ELECTRIFIED LOCK SPECIFICATIONS
Electrified locks contain a transistorized circuit which requires
24 volts AC or DC. Each lock should preferably have its own 24V
transformer. Two or more locks may be operated from a single
transformer, provided it has the necessary current rating.
NOTE: DO NOT connect locks in a series from a higher voltage
rated transformer.
We DO NOT recommend that these locks be connected to a
supply circuitthat also contains electromagnetic devices. If an
electromagnetic device is connected to the supply circuit, the
resulting transient voltages could damage the lock. The tran-
sient voltage must be carefully suppressed at the equipment
producing them before connecting the lock to the same circuit.
A varistor rated at 35 volts (peak recurrent) may be used for
transient voltage protection.
All installations should be in accordance with local electrical
codes and National Electrical Code NFPA #70-1978.
Electrical Requirements: Amps 1.3; Volts 24 AC or DC.
i
Solenoid
Operated
a
• @'
=========:-ii
Lock
!
Framato
Door Connector
~;
~II!
(notfurnished)
I
O
=>
I
••
JJ
Varistorwould
12_
-~
go hara if
used-_ -_
-_-_-_-:_~
Transformer
(not furnished)
(not furnished)
Switch
,...._ __ . . . . . r--,
_ _ _ _ _ _ 24_v_A_c-i
ll~ovAc
L__j
SERVICEL
MANUAL