    Contents Preparation for installation ....................................... 3 Deciding on where to install the indoor unit ................................4 Indoor unit installation ........................................7 Purging the unit ............................................. 8 Connecting the refrigerant pipe ....................................8 Cutting/Flaring the pipes ........................................9 Performing leak test & insulation ....................................10 Drainpipe and drain hose installation ..................................
  • Page 3: Preparation For Installation

    Our units should be installed in compliance with the spaces shown in the installation manual, to ensure accessibility from both disassemble without endangering people and objects. For this reason, when provisions of the installation manual are not complied with, the cost required to access and repair the units Power supply line, fuse or circuit breaker with current local safety standards.
  • Page 4: Deciding On Where To Install The Indoor Unit

    Preparation for installation Accessories The following accessories are supplied with the indoor unit. The type and quantity may differ depending on the specifications. Pattern sheet Thermal insulation Thermal insulation Thermal insulation Flexible hose clamp sponge B sponge C Flexible hose user manual Installation Conduit bracket...
  • Page 5 Thickness: more than 0.39inch(10mm) 009 / 012 / 018 / 020 Insulate the end of the pipe and some curved area by using separate insulator. Insulate the discharge and suction part at the same time when you insulate connection duct. either to guarantee correct operation of maintenance or repairing products.
  • Page 6 Deciding on where to install the indoor unit Drawing of the indoor unit 575(22.64) 300(11.81) 575(22.64) 200(7.87) 165(6.5) 249(9.8) Sub duct connection 269(10.6) Type B Model 24.41 22.03 22.83 1.87 0.89 10.71 10.94 Liquid pipe connection Drain Hose connection...
  • Page 7: Indoor Unit Installation

    Indoor unit installation When deciding on the location of the air conditioner with the owner, the following restrictions must be taken into account. 1. Determine the position of the pipe and drain hose hole as seen in the picture and drill the hole with an inner diameter of 65mm so that it slants slightly downwards.
  • Page 8: Purging The Unit

    Purging the unit before connecting the assembly piping. Unscrew the pinch pipe at the end of each refrigerant pipe. Liquid refrigerant port ready to connect the piping. Connecting the refrigerant pipe There are two refrigerant pipes of different diameters : The inside of copper pipe must be clean &...
  • Page 9: Cutting/Flaring The Pipes

    Cutting/Flaring the pipes 1. Make sure that you have the required tools available. (pipe cutter, reamer, flaring tool and pipe holder) 2. If you wish to shorten the pipes, cut it with a pipe cutter, taking care to ensure that the cut edge remains at a 90° angle with the side of the pipe.
  • Page 10: Performing Leak Test & Insulation

    Performing leak test & insulation Leak test To identify potential gas leaks on the indoor unit, inspect the connection area of each refrigerant pipe using a leak detector for R410A. Before recreating the vacuum and recirculating the refrigerant gas, it is advisable to pressurize the whole system with nitrogen (using a cylinder with pressure reducer) at a pressure above 40 bar in order to immediately detect leaks on the refrigerant fittings.
  • Page 11: Drainpipe And Drain Hose Installation

    When installing insulation in places and conditions below, use the same insulation that is used for high humidity conditions. e.g. The pipe installed at a corridor of a dormitory and studio or near an exit that opens and closes frequently. Drainpipe and drain hose installation 1 Push the supplied drain hose as far as possible over the drain socket.
  • Page 12: Installing Dpm

    Drainpipe and drain hose installation Concentrated drain pipe Testing the drainage Water leakage You should test the drainage after completing the installation. check part Prepare a little water about 2.0 liters. 1 Turn the cover drain pump, then pull it out. Hose 2 Pour water into the indoor unit as shown in figure.
  • Page 13: Bushing Bracket Installation

    Bushing bracket installation If the conduit tube is used, bushing bracket must be installed as shown in the picture to fix the conduit tube. Push Click 2 conduit tubes 1 conduit tube...
  • Page 14: Wiring Work

    Wiring work Power and communication cable connection Before wiring work, you must turn off all power source. outdoor power. MCCB : Molded Case Circuit Breaker The power cable should be used only copper wires. Wired Remote Controller MCCB+ ELCB V1 V2 ELCB : Essential Installation Power off before connecting any wires;...
  • Page 15 Specification of electronic wire Power MCCB ELB or ELCB Power cable Earth cable Communication cable supply 0.0039inch 0.0039inch 0.1 sec Rating current Rating Unit Model current X : The capacity of ELCB(or MCCB+ELB). AM FNND 0.17A Ai : Sum of Rating currents of each indoor unit. 0.19A Refer to each installation manual about the rating current of indoor unit.
  • Page 16 Wiring work(Cont.) Select the power cable in accordance with relevant local and national regulations. Wire size must comply with local and national code. For the power cable, use the grade of H07RN-F or H05RN-F materials. You should connect the power cable into the power cable terminal and fasten it with a clamp.
  • Page 17: Setting An Indoor Unit Address And Installation Option

    Setting an indoor unit address and installation option ▶ Set the indoor unit address and installation option with remote controller option. ▶ Please refer to the wired remocon installation manual for setting with the wired remocon. The procedure of setting option Air flow direction (Up and down) Power Turns the air conditioner on or off.
  • Page 18 Setting an indoor unit address and installation option Option setting Status Auto Auto ∨ ∧ will be selected in rotation. … 2. Setting Cool mode Cool Cool Cool ∨ ∧ will be selected in rotation. … 4. Setting Dry mode ∨...
  • Page 19 Option setting Status 12. Setting Cool mode Cool Press Mode button to be change to Cool mode in the OFF status. Cool Cool ∨ ∧ will be selected in rotation. … 14. Setting Dry mode Press Mode button to be change to Dry mode in the OFF status. ∨...
  • Page 20 Setting an indoor unit address and installation option Setting an indoor unit address (MAIN/RMC) 1(L) Check whether power is supplied or not. 2(N) power supply in the indoor unit. Before installing the indoor unit, assign an address to the indoor unit according to the air conditioning system plan.
  • Page 21 Setting an indoor unit installation option (suitable for the condition of each installation location) Check whether power is supplied or not. supply in the indoor unit. Set the installation option according to the installation condition of an air conditioner. indoor unit individually when there is more than one indoor unit. Set the indoor unit option by wireless remote controller.
  • Page 22 Setting an indoor unit address and installation option 1(L) 2(N) COM1 COM2 Wire Remote COIL Controller 02 series installation option(Detailed) Option No. : 02XXXX-1XXXXX-2XXXXX-3XXXXX Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Use of external room temperature Explanation PAGE MODE Use of robot cleaning sensor / Minimizing fan operation Use of central control FAN RPM compensation...
  • Page 23 Option SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 Setting the output of external Explana- Use of external PAGE control / External heater On/ S-Plasma ion Buzzer control Hours of filter usage tion control Off signal Auto Auto Cool Cool Remote Controller Display Details Setting the...
  • Page 24 Setting an indoor unit address and installation option 3: Fan is turned off when the hot water heater is turned on with cooling only indoor unit 2: Fan is turned on continually when the external heater is turned on, 3: Fan is turned off when the external heater is turned on with cooling only indoor unit controller sensor to detect indoor temperature exactly.
  • Page 25 05 series installation option(Detailed) Option No. : 05XXXX-1XXXXX-2XXXXX-3XXXXX Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 (When setting SEG3) Use of Auto Change (When setting SEG3) (When setting SEG3) Standard for mode Explanation PAGE MODE Over for HR only in Standard heating Standard cooling temp.
  • Page 26 Setting an indoor unit address and installation option Option Control variables when using hot water / external heater Remote Controller Display Details Indication Set temp. for heater On/Off Delay time for heater On 10 minutes 20 minutes 10 minutes 20 minutes Indication and Details 10 minutes...
  • Page 27 SEG 3, 4, 5, 6, 8, 9 additional information Standard temp. for Temp. → Heating Cooling Standard temp. for Cooling Set temp. for Auto mode Standard temp. for Heating Standard temp. A : Set with SEG4 → for Cooling B : Set with SEG5 Heating C : Set with SEG6 D : Set with SEG8...
  • Page 28: Final Check And Trial Operation

    Final check and trial operation To complete the installation, perform the following checks and tests to ensure that the air conditioner operates correctly. Check the following: Strength of the installation site Tightness of pipe connection to detect gas leak Drainage Providing information for user After finishing the installation of the air conditioner, you should explain the following to the user.