Height changes and T units
All changes ≤ 6 m are regarded as changes in height. With larger changes in height, the
guidelines for vertical planning must be taken into account.
Additional fixed points must be configured before or after changes in height and directly
at T units.
L ≤ 6 m
With a maximum height difference of 6 m, expansion compensation is not necessary.
SIVACON 8PS - Configuring with LX system
Configuration Manual, 10/2011, A5E02194899-02
Fixed point
6.2 Configuring the busbar run layout