Configuration
6.2 Configuring the busbar run layout
Load tap-off point from 800 A to 1,250 A
Load tap-off points from 800 A to 1,250 A can only be implemented for the system sizes
LXA(C)05..to LXA(C)10...
Size
1
2
3
4
①
②
③
④
104
Size 4 (800 A to 1250 A)
Straight length without tap-off points
Minimum length W
= 2000 mm
min
Tap-off joint block is used instead of the joint block on the trunking unit.
Fixing for joint block at front.
Tap-off unit with circuit breaker
≤ 250 A
315 ... 630 A
—
800 ... 1250 A
Configuration Manual, 10/2011, A5E02194899-02
Tap-off unit with fuse switch
disconnector
≤ 250 A
400 A
630 A
—
SIVACON 8PS - Configuring with LX system