Things To Check After Completing The Installation - Samsung AM***FXVAF Series Installation Manual

Dvm s
Hide thumbs Also See for AM***FXVAF Series:
Table of Contents

Advertisement

Things to check after completing the installation

1. Before supplying the power, use DC 500V (AM✴✴✴✴XV
tester to measure the power (3 phase: R, S, T) terminal and the outdoor unit grounding.
- Measurement should be over 30MΩ.
2. Before supplying the power, use a voltmeter and phase tester to check the voltage and the phase.
- R, S, T terminal: Check the 460V (AM✴✴✴✴XV
[AM✴✴✴
XV✴J✴]
T
460V
460V
S
460V
R
• Never measure the communication terminal since communication circuit may get damaged.
• Check for short-circuit of the communication terminal with a general circuit tester.
CAUTION
3. Check if the R-410A indoor units are connected.
4. Check the following after the installation is completed.
Outdoor unit
Installation work
Indoor unit
Refrigerant pipe work
Drain pipe work
J✴) or DC 600 V (AM✴✴✴✴XV
J✴) or 230V (AM✴✴✴✴XV
[AM✴✴✴
230V
230V
<ELB>
• Have you checked the external surface and the inside of the outdoor unit?
• Is there any possibility of short-circuit caused by the heat of an outdoor unit?
• Is the place well-ventilated and ensures space for service?
• Is the outdoor unit fixed securely to withstand any external force?
• Have you checked the external surface and the inside of the indoor unit?
• Is there enough space for service?
• Have you checked if the center of the indoor unit is ensured and it is installed
horizontally?
• Have you selected correct pipes?
• Are the liquid and gas valve open?
• Is the total number of connected indoor units within the allowable range?
• Are the length and the height difference between the refrigerant pipes
within the allowable range?
• Are the branch joints properly installed?
• Did you check the connection of liquid and gas pipes?
• Have you selected correct insulator for pipes and insulated them correctly?
• DId you insulate the pipes and connection part correctly?
• Is the quantity of the additional refrigerant correctly weighed in? (You must
record the amount of additional refrigerant on the service record paper
placed inside of the outdoor unit.)
• Have you checked if the drain pipes of the indoor and outdoor unit are
connected together?
• Have you completed the drain test?
• Is the drain pipe properly insulated?
F✴) insulation resistance
F✴) between wires (R-S, S-T, T-R)
XV✴F✴]
T
230V
S
R
<ELB>
97