Servicing - Worcester GREENSTAR SYSTEM FILTER Installation & Servicing Instructions Manual

For sealed & open vent central heating systems with 22mm central heating pipes

Advertisement

Always service the filter before leaving the
premises. The two large spanners should be
left with the customer.
4

SERVICING

NOTICE: Before commencing any servicing
work, turn off the electrical supply to the
boiler.
1. Turn both isolation valves to the marked OFF position.
Protect the surface below the system filter
with a suitable container to capture water.
2. Loosen the air vent to release the internal pressure.
– Then re- tighten the air vent.
Fig. 10 Close isolating valves
▶ Using the tool for body (larger of the two) steady the system
filter.
3. With the tool for cap gripping the base, loosen the base and
carefully unscrew.
Collect the filter contents in a container placed underneath
the filter.
6 720 803 839 (2012/11)
2.
1.
3.
Fig. 11
4. Remove the base [1] from the system filter, ensuring that
any water or debris is caught within the container.
5. Slide the magnetic cap sheath off the base [2].
▶ Wipe clean the magnetic cap sheath [2} and base [1].
▶ Reassemble the magnetic cap sheath onto the base section
and carefully screw the base section back into canister.
4.
1
Fig. 12
▶ Using the tool for body (larger of the two) steady the system
filter.
6. Using the tool for cap, grip the base and tighten until sealed,
do not over tighten.
SERVICING
5.
2
5