INSTALLATION
PRECAUTIONS
 Install the unit on a flat surface.
If the mounting surface is rough, undue force will be applied to the PC board,
thereby causing nonconformities.
 Install the product securely using a DIN rail or mounting screws.
 When drilling screw holes or wiring, make sure that cutting or wire debris
dose not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
 Be sure to remove the dust proof sheet from the PLC's ventilation port when
installation work is completed.
Failure to do so may cause fire, equipment failures or malfunctions.
 Connect extension cables securely to their designated connectors.
Loose connections may cause malfunctions.
2.1 Mounting
The FX
-ENET-L can be mounted directly using screws or on a DIN rail
3U
(DIN46227).
2.1.1
Direct Mounting
The FX
3U
-ENET-L can be mounted with M4 screws by using the direct mounting
holes.
A space of 1 to 2 mm (0.04" to 0.08") between each unit is necessary.
2.1.2
DIN Rail Mounting
The FX
3U
-ENET-L can be mounted on a DIN rail (DIN46227, 35 mm width).
1) Fit the upper edge of the DIN rail mounting
1)
groove (fig. A) onto the DIN rail.
2) Push the unit onto the DIN rail.
A
2.1.3
Procedure for connecting with the FX
Series PLC
3U
When connecting to an FX
:
3U
Before connections, turn off the power to the
1)
PLC.
1) Remove the extension device connector
cover of the main unit.
2) Fold and insert the extension cable in the
corresponding connector as shown to the
2)
right.
3) Reattach the extension device connector
cover on the main unit.
When connecting to an FX
:
3UC
Connector cover
When connecting the FX
-ENET-L,
3U
(A)
either the FX
-1PS-5V or FX
-
3UC
2NC
FX
-1PS-5V
3UC
CNV-IF is required.
1) The connector cover (A) of the
FX
-1PS-5V is removed as
3UC
shown in the figure to the right.
The FX
-CNV-IF does not have
2NC
a connector cover.
Extension cable on
2) Connect the extension cable as
the right side
shown to the right.
FX
-1PS-5V or
3UC
FX
-CNV-IF
2NC
3. Specification
For details on specifications, refer to the following manual.
Refer to the FX
-ENET-L User's Manual.
3U
DESIGN
PRECAUTIONS
 Make sure to include the following safety circuits outside the PLC to ensure
safe system operation even during external power supply problems or PLC
failure.
Otherwise, malfunctions may cause serious accidents.
1)Most importantly, have the following: an emergency stop circuit, a
protection circuit, an interlock circuit for opposite movements (such as
normal vs. reverse rotation), and an interlock circuit (to prevent damage
to the equipment at the upper and lower positioning limits).
2)Note that when the PLC main unit detects an error such as a watchdog
timer error, during self diagnosis, all outputs are turned off. Also, when an
error that cannot be detected by the PLC main unit occurs in an input/
output control block, output control may be disabled.
External circuits and mechanisms should be designed to ensure safe
machinery operation in such cases.
DESIGN
PRECAUTIONS
 Make sure to observe the following precautions in order to prevent any damage to
the machinery or accidents due to abnormal data written to the PLC under the
influence of noise:
1)Do not bundle the main circuit line together with or lay it close to the main
circuit, high-voltage line or load line.
Otherwise, noise disturbance and/or surge induction are likey to take place.
As a guideline, lay the control line at least 100mm (3.94") or more away from
the main circuit or high-voltage lines.
2)Ground the shield wire or shield of a shielded cable. However, do not ground
them at the same point as the high-voltage lines.
 Install module so that excessive force will not be applied to the unit or cables.
Failure to do so may result in wire damage/breakage or PLC failure.
STARTUP AND
MAINTENANCE
PRECAUTIONS
 Do not touch any terminals or connector while the PLC's power is on.
Doing so may cause electrical shock or malfunctions.
 Before cleaning or retightening screws, externally cut off all phases of the power
supply.
Failure to do so may cause malfunction or failure of this unit.
When the screws are tightened insufficiently, they may fall out and cause a short-
circuit or malfunction. When tightened too much, the screws or the unit may be
damaged, resulting in short-circuit, or malfunction.
 When controlling the PLC (especially when changing data, the program or
changing the operating conditions) during operation, ensure that it is safe to do
so.
STARTUP AND
MAINTENANCE
2)
PRECAUTIONS
 Do not disassemble or modify the unit.
Doing so may cause fire, equipment failures, or malfunctions.
 The unit case is made of resin. If dropped or subjected to strong impact, the unit
may be damaged.
 When this unit is installed or removed from the panel, make sure to externally cut
3)
off all phases of the power supply. Failure to do so may cause malfunction or
failure of this unit.
DISPOSAL
PRECAUTIONS
 Please contact a certified electronic waste disposal company for the
environmentally safe recycling and disposal of your device.
TRANSPORTATION AND
STORAGE PRECAUTIONS
 The product is a precision instrument. During transportation, avoid impacts larger
than those specified in the general specifications by using dedicated packaging
boxes and shock-absorbing palettes.
Failure to do so may cause failures in the product.
After transportation, verify operation of the product and check for damage of the
mounting part, etc.
Items other than the following are equivalent to those of the PLC main unit.
For general specifications, refer to the manual of the PLC main unit.
Refer to the FX
3U
Series User's Manual - Hardware Edition.
Refer to the FX
Series User's Manual - Hardware Edition.
3UC
Item
Specifications
0 to 55C (32 to 131F) when operating and -20
Ambient temperature
to 75C (-4 to 167F) when stored
General
Dielectric withstand
500 V AC for one minute
specifi-
voltage
cation
5 M or higher by 500 V
Insulation resistance
DC insulation resistance
tester
Data transmission
100 Mbps
speed
Communication
Full-duplex/Half-duplex
method
Trans-
mission
Transmission method
Base band
specifi-
cations
Maximum segment
100 m (328'1")
*1
length
Maximum number of
Cascade connection
nodes/connection
Maximum 2 stages
Item
Fixed buffer
communica-
2 connections
Number of
tion
simultaneously
open connections
M E L S O F T
allowed
connection +
A total of 2 connections
MC protocol
1023 word  2
Trans-
Fixed buffer
mission
Attached file
2048 word  1
data
E-mail
storage
*2*3
Main text
256 word  1
memory
Number of I/O occupied points
8 points
24 V DC
240 mA, 24 V DC +20%, -15%,
external power supply
ripple (p-p) less than 5%
Allowable
I n s t a n t a -
Operation can be continued upon occurrence of
Power
neous power
instantaneous power failure for 1 ms or less.
supply
failure time
specifi-
cations
5 V DC of PLC is not used.
(5 V DC is converted from 24 V DC external
5 V DC
power supply.)
internal power supply
Make sure to observe the power-on timing and
the procedure.
90(H)  55(W)  87(D) [mm]
External dimensions
3.55"(H)  2.17"(W)  3.43"(D) [inches]
MASS (Weight)
Approx. 0.3 kg (0.66 lbs)
Number of connectable units to
1
the main unit
*1 Length between a hub and a node.
*2 Refer to the FX
-ENET-L User's Manual of e-mail sending function
3U
specifications.
*3 It is not possible to send an attached file and main text simultaneously.
3.1 Applicable PLC
Model name
Ver. 2.21 and later
FX
Series PLC
3U
Only one FX
3U
-ENET-L unit can be connected in a main unit.
Ver. 2.21 and later
FX
Series PLC
*1
3UC
Only one FX
3U
-ENET-L unit can be connected in a main unit.
The version number can be checked by reading the last three digits of device D8001/
D8101.
*1 An FX
-CNV-IF or FX
-1PS-5V is necessary to connect the FX
2NC
3UC
with the FX
PLC.
3UC
3.2 Related software
Model name
FX Configurator-EN-L
*1
Ver. 1.00 and later
GX Works2
Ver. 1.09K and later
GX Developer
Ver. 8.88S and later
*1 To use FX Configurator-EN-L, either of the following software should be installed.
- GX Works2(Ver. 1.09K or later)
- GX Developer (Ver. 8.88S or later)
4. Wiring
WIRING
Between all
PRECAUTIONS
terminals and the
 Make sure to cut off all phases of the power supply externally before
ground terminal
attempting wiring work.
Failure to do so may cause electric shock or damage to the product.
10 Mbps
WIRING
PRECAUTIONS
 Before wiring the unit, confirm that the rated voltage and terminal allocation
of the unit are correct. An incorrect voltage supply and/or incorrect wiring
may cause fire, malfunction, or failure.
 Perform class D grounding (grounding resistance: 100 or less) to the
grounding terminal on the main unit.
Do not use common grounding with heavy electrical systems.
Cascade connection
 Prevent cutting or wiring debris from entering the main unit. Failure to do so
Maximum 4 stages
cause fire, malfunctions, or failures.
4.1 Grounding
Specifications
Other
PLC
equipment
Independent grounding
(Best condition)
Wiring and power supply wiring between PLC and FX
Example usage of FX
3U
D Grounding
(100 Ω or less)
FX
3U
电器电子产品有害物质限制使用标识要求」的表示方式
Note: This symbol mark is for China only.
含有有害6物质的名称, 含有量, 含有部品
 本产品中所含有的有害 6 物质的名称, 含有量, 含有部品如下表
所示。
产品中有害物质的名称及含量
部件名称
Applicability
(Pb)
外壳
可编程
控制器
印刷基板
本表格依据SJ/T 11364的规定编制。
○:表示该有害物质在该部件所有均质材料中的含量均在GB/T 26572
-ENET-L
3U
规定的限量要求以下。
×:表示该有害物质至少在该部件的某一均质材料中的含量超出GB/T
26572规定的限量要求。
Applicability
基于中国标准法的参考规格:GB/T15969.2
This manual confers no industrial property rights or any rights of any other kind,
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
Warranty
Exclusion of loss in opportunity and secondary loss from warranty liability
Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation to:
(1) Damages caused by any cause found not to be the responsibility of Mitsubishi.
(2) Loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products.
(3) Special damages and secondary damages whether foreseeable or not, compensation for
accidents, and compensation for damages to products other than Mitsubishi products.
(4) Replacement by the user, maintenance of on-site equipment, start-up test run
and other tasks.
This product has been manufactured as a general-purpose part for general
industries, and has not been designed or manufactured to be incorporated in
a device or system used in purposes related to human life.
Before using the product for special purposes such as nuclear power, electric
power, aerospace, medicine or passenger movement vehicles, consult with
Mitsubishi Electric.
This product has been manufactured under strict quality control. However
when installing the product where major accidents or losses could occur if the
product fails, install appropriate backup or failsafe functions in the system.
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Other
Other
PLC
PLC
equipment
equipment
Shared grounding
Common grounding
(Good condition)
(Not allowed)
-ENET-L
3U
Externally power supply for FX
-ENET-L
3U
24V DC
24+
Ethernet
24-
modular jack
(RJ-45)
ENET-L
LAN
HUB
有害物质
多溴
六价铬
多溴联苯
二苯醚
(Hg)
(Cd)
(Cr(VI))
(PBB)
(PBDE)
×
For safe use