4. Installation Instructions
4-4. Outdoor Unit
AVOID:
heat sources, exhaust fans, etc.
damp, humid or uneven locations.
Indoor (no ventilation place)
DO:
choose a place as cool as possible.
choose a place that is well ventilated.
allow enough room around the unit for air intake/ exhaust
and possible maintenance.
Installation space
Install the outdoor unit where there is enough space for
ventilation. Otherwise the unit may not operate properly. Fig.
2-10 shows the minimum space requirement around the
outdoor units when three sides are open and only one side is
shuttered, with areas over the unit open. The mounting base
should be concrete or a similar material that allows for
adequate drainage. Make provisions for anchor bolts,
platform height, and other site-specific installation require-
ments.
CAUTION
NOTE
* Do not do any wiring or tubing within 60 cm of the front
panel, because it is needed as a servicing space for the
compressor.
Multiple installation
One units in two row
Min.
0.9 m
0.6 m
Min.
0.9 m
Min.
Min.
0.9 m
0.9 m
1671_C_I
One units in three row
Min.
1.1 m
0.6 m
0.6 m
Min.
1.1 m
Min.
Min.
1.1 m
1.1 m
1672_C_I
Conditions for installation: Fence height 1.8m, Effective opening ratio 50%, No raising for installation.
The distances between the units will vary with changes in installation conditions.
Not more than 2 units
should be installed
adjacently.
Leave space open above
the unit.
Construct louvers or other
openings in the wall, if
necessary, to ensure
adequate ventilation.
Two sets by two rows
(Total four sets)
Min.
0.66 m
Min.
1.3 m
1.3 m
Two sets by three rows (Total
six sets)
Min.
0.66 m
Min.
2.1 m
2.1 m
II - 27
Design of W-ECO MULTI SYSTEM
Hot air
Out-
door
unit
PC and AD unit placed adjacently
Min. 50 cm
Three sets by two rows (Total
Min.
1.3 m
1.0 m
Min.
1.3 m
Min.
0.66 m
1.6 m
1673_C_I
Three sets by three rows
(Total nine sets)
Min.
2.1 m
1.0 m
1.0 m
Min.
2.1 m
Min.
0.66 m
2.2 m
1674_C_I
Exhaust fan
Heat
source
0024_C_I
Min. 50 cm
Min. 13 cm
1670_C_I
six sets)
Min.
1.6 m
1.5 m
Min.
1.6 m
0.66 m
Min.
1.6 m
1675_C_I
Min.
2.2 m
1.5 m
1.5 m
Min.
2.2 m
0.66 m
Min.
2.2 m
1676_C_I
TD831077