SECTION 16: REMOVAL AND REPLACEMENT PARTS

See warnings and notes on Page 27 , Section 13
before removing or replacing parts.
Burner Components
All serviceable burner parts are accessed by the
door on the side of the heater.
See Page 5, Section 4.

16.1 Gas Valve

The VR4605 gas valve is fitted with the V7335A
modureg regulator (P/N L512) supplied as a
separate component.
When replacing the gas valve the modureg will need
to be fitted on site. To fit the modureg, remove the
standard regulator by removing the two screws
retaining the rubber sealing washer. See Page 35,
Figure 17
16.1.1 Gas Valve Replacement - (all models)
Description
Part Number
Gas Valve VR4605
Ignition Control
16.1.2 Gas Valve Replacement continued- (all models)
Replace in reverse order. Verify that the gas flow
direction of the valve is correct. Re-use the "O" ring
seal in the outlet flange where fitted. Check that all
the joints are leak free. Reset gas valve.
See Page 23, Section 11.4.2.
IT IS IMPORTANT THAT ONLY THE CORRECT
GAS VALVES SPECIFIED FOR EACH MODEL
TYPE ARE USED WHEN REPLACING THESE
CONTROLS.
90033404
90434020
SECTION 16: R

Figure 17: Standard Regulator Removal

Fit the modureg ensuring that the rubber seal is in
place and the two screws are tight. See Page 35,
Section 16.1.1. Once fitted follow commissioning
procedure in Section 11.
R
EMOVAL AND
EPLACEMENT
P
ARTS
35