Failure mode
Ignition failure
Version 1.0
Cause
1. Check the primary/secondary power supply to the main gas valve.
Check, with a multi-meter, between the RED-YELLOW and WHITE-RED wires to verify
that the input power is DC 22-24V
2. Replace the PCB if power is not supplied.
Main gas valve
3. If power supply is normal, check if the coil is open.
Check the resistance.
4. Check if the solenoid valve works properly.
Feel or hear a click
PIN No.
Check if the coil is open (Proper resistance range : 100~1,000 Ω)
Check the voltage of the solenoid valve / Red-Yellow, White-Red
Check method
NHB Service Manual
89