Navien NHB-055 Service Manual page 24

Nhb series condensing boilers
Table of Contents

Advertisement

Maximum Liquefied Propane Delivery Capacity
In Thousands of BTU / H (0.5" WC Pressure Drop)
Length (including fittings)
Pipe Size
10 ft.
20 ft.
(3 m)
(6 m)
/
in
291
200
1
2
/
in
608
418
3
4
1 in
1,150
787
1
/
in
2,350
1,620
1
4
1
/
in
3,520
2,420
1
2
2 in
6,790
4,660
The inlet gas pressure must be maintained between 3.5 in and 10.5 in WC for natural gas and between 8.0 in and 13.5 in WC for liquefied
propane.
The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that
system at test pressures in excess of
The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of
the gas supply piping system at test pressures equal to or less than
NOTE
For installations using CSST (flexible) gas piping, please refer to the sizing charts provided by the manufacturer.
The use of single-stage regulators are recommended. Dual-stage regulators could cause operational issues with the boiler.
24
NHB Service Manual
30 ft.
40 ft.
50 ft.
(9 m)
(12 m)
(15 m)
160
137
122
336
287
255
632
541
480
1,300
1,110
985
1,940
1,660
1,480
3,750
3,210
2,840
/
psi (3.5 kPa).
1
2
60 ft.
70ft.
80ft.
(18 m)
(21m)
(24m)
110
101
94
231
212
197
434
400
372
892
821
763
1,340
1,230
1,140
2,570
2,370
2,200
/
psi (3.5 kPa).
1
2
90ft.
100ft.
125ft.
(27m)
(30m)
(38m)
89
84
74
185
175
155
349
330
292
716
677
600
1,070
1,010
899
2,070
1,950
1,730
200 ft.
250 ft.
(60 m)
(76 m)
67
62
140
129
265
243
543
500
814
749
1,570
1,440
Version 1.0

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nhb-080Nhb-110Nhb-150

Table of Contents