10.1 Valid Ranges for the S7-200 CPUs

Table 10-1
Summary of S7-200 CPU Memory Ranges and Features
Description
User program size
512 words
User data size
512 words
Process-image input register
I0.0 to I7.7
Process-image output
Q0.0 to Q7.7
register
Analog inputs (read only)
AIW0 to AIW30
Analog outputs (write only)
AQW0 to AQW30
Variable memory (V)
V0.0 to V1023.7
Permanent area (max.)
V0.0 to V199.7
Bit memory (M)
M0.0 to M15.7
Permanent area (max.)
MB0 to MB13
Special Memory (SM)
SM0.0 to SM45.7
Read only
SM0.0 to SM29.7
Timers
64 (T0 to T63)
Retentive on-delay
1 ms
T0
Retentive on-delay
10 ms
T1 to T4
Retentive on-delay 100 ms
T5 to T31
On-delay
1 ms
T32
On-delay
10 ms
T33 to T36
On-delay
100 ms
T37 to T63
Counters
C0 to C63
High speed counter
HC0
Sequential control relays
S0.0 to S7.7
Accumulator registers
AC0 to AC3
Jumps/Labels
0 to 63
Call/Subroutine
0 to 15
Interrupt routines
0 to 31
Interrupt events
0, 1, 8 to 10, 12
PID loops
Not supported
Ports
0
10-2
CPU 212
CPU 214
2 Kwords
2 Kwords
I0.0 to I7.7
Q0.0 to Q7.7
AIW0 to AIW30
AQW0 to AQW30
V0.0 to V4095.7
V0.0 to V1023.7
M0.0 to M31.7
MB0 to MB13
SM0.0 to SM85.7
SM0.0 to SM29.7
128 (T0 to T127)
T0, T64
T1 to T4, T65 to T68
T5 to T31, T69 to T95
T32, T96
T33 to T36,
T97 to T100
T37 to T63,
T101 to T127
C0 to C127
HC0 to HC2
S0.0 to S15.7
AC0 to AC3
0 to 255
0 to 63
0 to 127
0 to 20
Not supported
0
CPU 215
4 Kwords
4 Kwords
2.5 Kwords
2.5 Kwords
I0.0 to I7.7
I0.0 to I7.7
Q0.0 to Q7.7
Q0.0 to Q7.7
AIW0 to AIW30
AIW0 to AIW30
AQW0 to AQW30
AQW0 to AQW30
V0.0 to V5119.7
V0.0 to V5119.7
V0.0 to V5119.7
V0.0 to V5119.7
M0.0 to M31.7
M0.0 to M31.7
MB0 to MB13
MB0 to MB13
SM0.0 to SM194.7
SM0.0 to SM194.7
SM0.0 to SM29.7
SM0.0 to SM29.7
256 (T0 to T255)
256 (T0 to T255)
T0, T64
T0, T64
T1 to T4, T65 to T68
T1 to T4, T65 to T68
T5 to T31, T69 to T95
T5 to T31, T69 to T95
T32, T96
T32, T96
T33 to T36,
T33 to T36,
T97 to T100
T97 to T100
T37 to T63,
T37 to T63,
T101 to T255
T101 to T255
C0 to C255
C0 to C255
HC0 to HC2
HC0 to HC2
S0.0 to S31.7
S0.0 to S31.7
AC0 to AC3
AC0 to AC3
0 to 255
0 to 255
0 to 63
0 to 63
0 to 127
0 to 127
0 to 23
0 to 26
0 to 7
0 to 7
0
0 and 1