Boiler Location - QUINCY HYDRONIC TECHNOLOGY SG-3 Installation Instructions And Instructions For Use

Sg pro series packaged boiler
Table of Contents

Advertisement

Biasi SG Pro Series
The following are the minimum clearance to construction or combustible materials:
1. 9" from the top, sides, and rear of the boiler.
2. 18" from the flue pipe in any direction.
3. 24" inches from the front of the boiler.
The boiler must be located on a non-combustible floor. A smooth, level concrete floor
is recommended. Locate the boiler as close as possible to the chimney. The length of the
chimney connector may not exceed a distance of chimney height less ten feet. If boiler is
installed on combustible flooring, consult local authorities for proper method of covering floor.
The boiler must not be installed on carpeting.
Caution: Do not store or use flammable materials, chemicals or flammable
liquids, especially gasoline, in the vicinity of this heating appliance.
If the boiler is to be installed in "direct vent" configuration, please refer
to the QHT Direct Vent Addendum supplied with the Direct Vent Kit
available at www.qhtinc.com.
PROVISIONS FOR COMBUSTION AIR AND VENTILATION AIR MUST BE IN ACCORDANCE
WITH SECTION 5.3, AIR FOR COMBUSTION AND VENTILATION, OF THE NATIONAL FUEL
GAS CODE, ANSIZ223.1, OR APPLICABLE PROVISIONS OF THE LOCAL BUILDING
CODES. DO NOT INSTALL THE BOILER UNTIL PROPER COMBUSTION AIR HAS BEEN
ARRANGED.
Boiler is certified as an indoor appliance. Do not install boiler outdoors or locate where it will be
exposed to freezing temperatures

3. Boiler Location

DANGER
WARNING