Page 1
These instructions are available in English and French. Please keep these instructions for future reference. Gas Condensing Stainless Steel Boiler SSB BOILER SSB85 | SSB120 | SSB160 Service Manual...
► Immediately correct all faults to prevent system damage. Observe these instructions for your safety. ► Only use original Bosch spare parts. Losses caused by the use of The burner and control must be correctly installed and adjusted to ensure parts not supplied by Bosch are excluded from the Bosch warranty.
► The boiler is intended only for the use for which it was specifically central heating systems. Any other use is prohibited. designed and built. Bosch is hereby excluded from any liability for damages caused to persons, animals or property resulting from •...
Product description | 5 2 .3 Start/Stop cycle Fig. 1 Burner ignition cycle diagram If flame is detected at the end of the pre-spark period (Ignit_0) a lockout error occurs (This lockout has a maximum of 3 auto False flame detection resets).
Main components | 7 Main components Fig. 3 Main components [1] Main power switch [15] High limit temp. safety switch [2] System return [16] Heat exchanger [3] Gas inlet [17] Condensate trap [4] Flue exhaust [18] Low point drain valve [5] Intake air [19] Circulation pump [6] System supply...
8 | Main components 4 .1 Burner head 4 .2 Heat exchanger The burner head (Fig. 4) is made of stainless steel, it supports a micro The heat exchanger (Fig. 7) is a single coil design made of stainless premix flame. The burner can be accessed by removing the larger four steel.
Main components | 9 4 .5 Low Water Cut Off (LWCO) Return temperature sensor The Low Water Cut off (LWCO) is installed on the supply pipe, at the highest position available. Using a dedicated wet sensor it checks the minimum level of water inside the boiler by way of an electrical signal ground.
The gas valve regulates the air/fuel ratio on the basis of combustion air delivery (the air/fuel ratio is 1:1). Fig. 17 Venturi SSB85 - SSB120 Component [1] Fan [2] Venturi [3] Air inlet [4] Gas inlet Tab. 2 Venturi SSB85 - SSB120 Fig. 15 Gas valve SSB85 - SSB120 6720866940 (2017/11) US...
Main components | 11 4 .13 Flue pressure switch Flue pressure switch is a safety device designed to turn off the burner in case of block vent (for example due to obstruction of condensate drain). The silicon pipe is connected on one end to the “+” port of pressure switch (Fig.
Pressure relief valve The boiler is protected by a relief valve against overpressure. The 3/4” discharge outlet must be piped per local code requirements. Boiler model Pressure value SSB85 30 psi (2,07 bar) SSB120 30 psi (2,07 bar) SSB160 30 psi (2,07 bar) Tab.
Control Panel (LCD Display) | 13 5 .2 Date and time setting Control Panel (LCD Display) Press the “menu” button and select “Settings” using the arrow buttons to select “Settings”. The homepage on the display shows the basic status of the boiler. Menu Domestic Hot Water Information...
14 | Control Panel (LCD Display) Entering the “Time Zone Settings” menu it is possible to set the time zone Fig. 33 parameter as shown on the following figure: CH and the DHW setpoint can be edit directly from the homepage of the display.
Control Panel (LCD Display) | 15 5 .6 Parameters list Press “OK” and the display will show the following information: • Supply Temperature To have access to the parameter list press “menu” button and select “Settings” using the “UP/DOWN” keys “ / ”. •...
Page 16
Boiler Rotation Interval Days DHW Boiler Assign Tab. 7 Level 2 parameters (INSTALLER) (*) Depend on appliance type (**) The value for this parameter is: • 4 for SSB160 • 5 for SSB120 • 6 for SSB85 6720866940 (2017/11) US...
Parameters description | 17 Minimum CH and DHW power Parameters description (Also applicable to all other CH and DHW Modes) The minimum burner power during operation can be limited with 6 .1 Central Heating (CH) parameter P_Min. CH_Mode=1 Request for Heat with Outdoor Sensor and Room thermostat.
18 | Parameters description 6 .2 Domestic Hot Water Par .22: Baseline Outdoor Temp . Defines the maximum outdoor temperature to calculate the minimum Par .35 DHW_Mode supply temperature for CH Mode=0 No Domestic Hot Water Mode=1 External DHW tank with temperature probe. Par .23: Min Supply Temp .
Page 19
Parameters description | 19 Par .36 DHW Tank Hyst Down The differential for the DHW tank load. If the temperature decrease below “Par.48 DHW_Setpoint”–Par. 36 DHW_Hist_Down”, the call for heat is activated igniting the burner. Par .37 DHW Tank Hyst Up Differential setpoint for shutting off the call for heat.
[8] Verify all electrical connections are correct; [9] Verify no electrical components were removed or tampered with; Fig. 49 Installation location for the LPG orifice - model SSB85 - SSB120 [10] Fill the condensate trap with water and ensure a continuous downward slope exists in the outlet tube.
Page 22
Orifice Venturi Gasket Orifice Fig. 51 Valve configuration - model SSB85 - SSB120 Gasket Use the control panel to enter in the parameter list and change the parameter no. 98 (Gas Type) from “NG” to “LPG”. Adjust the CO level according to the values shown in Tab.
(all models); Inner Diameter LPG Orifices (mm) System Test Test State High Power Boiler model Inner diameter LPG orifices (mm) Fan Speed 0 rpm SSB85 5.5 Ø SSB120 5.0 Ø Ionisation 0.0 μA SSB160 6.25 Ø Tab. 8 Gas Orifice Diameter Fig.
Combustion test Verify condition of flue and air system Annually * (including Venturi and fan) Annually * Check ignition electrode Fig. 61 Connectors SSB85 - SSB120 Cleaning the combustion chamber (including Annually * the burner tube) Annually * Clean condensate discharge...
Page 25
[4] Remove the fan unscrewing the 4 nuts that fix it to the heat exchanger (see picture below showing 3 out of 4 nuts); Fig. 63 Air inlet hose SSB85 - SSB120 Air inlet hose Fig. 67 Fan - 4 nuts [5] Remove the fan;...
26 | Maintenance schedule & procedures [6] Remove the gasket; [3] Remove the exchanger top cap (including the insulation); Gasket Top cap + insulation Fig. 69 Gasket [7] Pull out the burner head. Rotate the burner head to align the mark (A) to the igniter (B);...
Page 27
Maintenance schedule & procedures | 27 Kit Contents: [8] Using the brush remove debris from the spiral tubes, vacuum the debris from the heat exchanger, without damaging the calorite disc; - 1 x Manual water pump and wand - 1 x Calorite disc protector plate - 1 x Bottle Atomizer Brush - 1 x Cleaning Brush...
28 | Maintenance schedule & procedures 8 .6 Cleaning the Ignition Electrode 8 .7 Inspection, replacement and features of supply, return and flue NTC temperature sensors The ignition electrode requires annual maintenance to remove any potential oxide layer that may be generate during normal operation. The NTC sensor transduces a temperature value into an electrical Check the high voltage cable for cracks and oxidation on the plug.
Maintenance schedule & procedures | 29 Electrical supply Temperature °F (°C) Resistance [Ω] Testing tolerance ±10% 9 .1 Electrical supply wiring 32 (0) 27396 Connect the boiler to the main electrical supply, as required by local, state 41 (5) 22140 and federal codes.
Electrical supply | 31 9 .8 Electrical wiring diagram Jumper factory installed LOW VOLTAGE HIGH VOLTAGE HIGH IN / OUT VOLTAGE PUMP CH PUMP DHW 120 V Supply CASCADE Room MAIN PUMP ALLARM 120 V AUX Sensor MAIN IN Tank LINK SWITCH DOOR...
32 | Electrical supply 9 .9 Lockout errors list If an error is a “Lockout” error, it is necessary to press “RESET” button (after eliminating the reason for the failure) to restart the boiler. In the following table the “Lockout” errors are listed: Error Int .
Electrical supply | 33 Error Int . nr . Description Checks Solutions a- Check the integrity of Three times flame lost during one the wire connections of the a- If wires are damaged, replace "Too Many Flame Failures" demand spark and the earth on heat them exchanger "Flow Switch Not Closed Error"...
Page 34
34 | Electrical supply Error Int . nr . Description Checks Solutions a- Change the pump or restart it a- Check the pump to verify b- Open the valves on hydraulic the flow circulation circuit b- Check if the valves on “Overheat Error”...
Electrical supply | 35 9 .11 Errors not shown on display Symptoms Possible solutions Check gas type. Combustion noise too loud; rumbling noises Check inlet gas pressure; adjust as needed. Check flue gas system; clean or repair as needed. Check gas/air ratio in the combustion air and flue gas; replace gas valve as needed. Set pump speed correctly to match maximum output.
Page 36
36 | Spare parts Spare parts Fig. 88 6720866940 (2017/11) US...
Page 37
7-738-004-907 Mounting bracket control board panel ■ ■ ■ 7-738-004-908 Alignment pin front side panels ■ ■ ■ 7-738-004-924 Logo Bosch front door ■ ■ ■ 7-738-005-176 Handle front panel ■ ■ ■ 7-738-004-920 Lock and lever front panel ■...
Page 38
38 | Spare parts Shown on Fig. 91 - Fig. 92 Fig. 89 6720866940 (2017/11) US...
Page 39
Spare parts | 39 Item (→ Fig. 89) Description Order number High limit sensor and screws ■ ■ ■ 7-738-004-926 Universal temperature detector and washer ■ ■ ■ 7-738-004-930 O-ring temperature detector 0.51x0.1in 13x2.62mm ■ ■ ■ 7-738-004-931 Automatic air vent 3/8" ■...
Page 41
Spare parts | 41 Item (→ Fig. 90) Description Order number Enclosure user interface ■ ■ ■ 7-738-005-037 Circuit Board user interface ■ ■ ■ 7-738-005-038 Keypad ■ ■ ■ 7-738-005-039 Service plug cover ■ ■ ■ 7-738-005-040 On Off power switch ■...
Page 43
7-738-005-400 Gasket burner flange inner ring to fan ■ ■ 7-738-004-990 Fan + Venturi ■ ■ 7-738-005-159 Gasket venturi tube / gas valve SSB85/120 ■ ■ 7-738-005-409 Gas valve and washers ■ ■ 7-738-005-160 Washer gas pipe 3/4” 19.05mm ■...
Page 44
44 | Spare parts SSB160 ONLY Fig. 92 6720866940 (2017/11) US...
Page 45
Spare parts | 45 Item (→ Fig. 92) Description Order number Heat exchanger SSB160 ■ 7-738-005-156 Washer for ignition electrode ■ 7-738-005-034 Ignition electrode with washer ■ 7-738-005-397 Sight glass for combustion ■ 7-738-005-031 Gasket premix burner tube ■ 7-738-004-985 Premix burner tube ■...
Page 46
46 | Spare parts Notes 6720866940 (2017/11) US...
Page 47
Spare parts | 47 6720866940 (2017/11) US...
Page 48
United States and Canada Bosch Thermotechnology Corp. 50 Wentworth Avenue Londonderry, NH 03053 Tel. 603-552-1100 Fax 603-965-7581 www.boschheatingandcooling.com U.S.A. Bosch Thermotechnology Corp. reserves the right to make changes without notice due to continuing engineering and technological advances.