8.1

Cable data

Description
Cable for standard electrode or coil
Electrode cable, double shielded
Cable kit with standard coil cable and electrode cable double
shielded (also available as low noise cable for MAG 1100
sensor )
Standard applications
Table 8- 8
Basic data
Max. cable loop resistance
Cable glands on sensor
and transmitter
Special applications, e.g. low conductivity or electrical noise
Table 8- 9
Basic data
SITRANS F M MAG 3100
Operating Instructions, 06/2010, A5E03005599-01
Technical data, standard application cables
No. of conductors
Min. sqr. area
Shield
Max. capacitance
Media temperature:
< 100 °C
> 200 °C
M20x1.5 gland - Cable ø 5 ... 13 mm (0.20 ... 0.51 inches)
½ NPT gland - cable ø 5 ... 9 mm (0.20 ... 0.35 inches)
Technical data, special application cables
No. of conductors
Sqr. area
Shield
Color code
Outside color
Ext. diameter
Conductor
Isolation material
Coil cable
2
0.5 mm
2
Yes
N/A
40 Ω
6 Ω
Coil cable
Special electrode cable
3
1.5 mm
2
Yes
Brown, blue, black
Grey
7.8 mm
Flexible CU
PVC
Technical data
8.1 Cable data
Standard electrode
cable
3
0.2 mm
2
Yes
350 pF/m
N/A
N/A
3
0.25 mm
2
Double
Brown, blue, black
Grey
8.1 mm
Flexible CU
PVC
53