Toshiba UC1A1A020C6TB Operation Manuals page 16

1400se series; 1400se plus series. single phase - 2.0/2.4 kva plus
Table of Contents

Advertisement

TOSHIBA
4.0
Specifications
4.1
Plus Series Specifications (Cont'd)
Input
Battery
Battery backup time when fully charged
with 0.7 power factor at77° F (25° C)
Output
Output voltage regulation
Output voltage waveform
Rated load power factor
Voltage transient characteristic
Rated output current (rms)
Maximum output current (peak)
Inverter overload capacity
Environment
External dim.s (2.4KVA 208/240V)
Switches
Interfaces
Fault detect and input power loss
Options
Software for unattended
(*) Output capacity reduced when input voltage is between -15% and -30% of nominal.
(**) Battery backup time may vary depending on the operating conditions and ambient temperature at the
installation site.
(***) An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is used
for battery backup.
(****) At 6000 ft (2000 m) above sea level, output capacity should be derated by 3%.
MODEL NUMBER
UC1G2L024C6TB
CAPACITY
2400 VA (1.68 kW)
Input voltage
Single phase, 208/240 Vac, +10% to -30% (*)
Input frequency
45 to 65 Hz
Input capacity
2400 VA
Input power factor
Approximate unity (0.98 to 1.0)
Battery rated voltage
96 Vdc
7 min. at full load (**)
30 min. at half load (**)
Recharge time
Maximum 24 hrs to 100% (90% recharge after 8 hrs) (***)
Type of batteries
Sealed lead-acid
Output voltage
Single-phase, 240/208/120 volts
Within +/- 3%, steady state
Output frequency
50/60 Hz +/- 0.5% in free-running mode (line sync range +/- 1Hz)
Computer-grade sine wave with less than 3.0% total harmonic
distortion with linear load
0.7 lagging (0.6 to 1.0)
+/- 5% under 100% load step change
10.0A
30.0A
150% for 60 seconds
Crest factor
3.0
Operating temperature
32 to 104° F (0 to 40° C), optimal at 77° F (25° C)
Storage temperature
-4 to 104° F (-20 to 40° C)
Operating humidity
30 to 90%, no condensation
Altitude(****)
Less than 3000 ft (1000 m) above sea level
10.00W x 25.50D x 22.50H (254W x 648D x 572Hmm)
Net weight
150 lb (68.2 kg)
Acoustical noise
45 dB at max. output, measured 3.3 ft (1 m) from front panel
Efficiency (ac-dc-ac)
85%
Bypass switch
Automatic bypass is provided when the run switch is in the off
position, if a fault occurs, or if an overload occurs (transfer time is
approximately 4 mS)
IBM (TM) AS/400
Pins 5 through 9
LAN Manager
Pins 2 and 3
Pins 1 and 4
RS232 ASCII
Pins 1 through 8
computer shutdown
Contact Toshiba for details on this option
External battery pack
Contact Toshiba for details on this option
DB9 male connector
DB9 female connector (Pin 9 not used)