15
Current setpoint - cooling
This data item forms the 2-byte KNX object and can be sent and received. It is relevant
for setpoint management and for calibration of setpoint offsets between devices.
This object is used for displaying the current setpoint, e.g. for display and diagnostics.
16
Current setpoint - heating
This data item forms the 2-byte KNX object and can be sent and received. It is relevant
for setpoint management and for calibration of setpoint offsets between devices.
This object is used for displaying the current setpoint, e.g. for display and diagnostics.
17
Object Switching for reset
This 1-bit communication object is enabled, if the proper parameter has been set to „yes".
This object resets the comfort setpoint to the parametrised value.
This data item forms the 1-byte KNX object and can be received only. Manual operation
is reset when a „1" is received.
18
Base setpoint
Object is visible if the dependent setpoint preset has been set in the parameters.
This data item forms the 2-byte base setpoint KNX object and can be received. It is relevant
for the concept of the dependent setpoint adjustment and is not used with absolute setpoints.
It can also be used to reset the manual on-site adjustment if this function is parametrised.
The setpoint is qualified via application parameters if „heating and cooling" is selected.
The base setpoint can then be defined as SPB heating, SPB cooling or centre of dead zone.
If only heating or only cooling is enabled, the SPB corresponds to the operating mode.
mode.
19
High additional heat. adj.
This data item forms the 1-byte or 1-bit KNX object and can be sent only. This object represents the control value
for the additional cooling stage (switching or quasi-continuous).
27
Comfort setpoint - heating
Object is visible if the individual setpoint preset has been set in the parameters.
This data item forms the 2-byte KNX object and can be received. It is relevant for absolute
setpoint management. When a setpoint for an operating mode is received,
setpoint is automatically enabled.
28
Standby setpoint - heating
Object is visible if the individual setpoint preset has been set in the parameters.
This data item forms the 2-byte KNX object and can be received. It is relevant for absolute
setpoint management. When a setpoint for an operating mode is received,
setpoint is automatically enabled.
29
Night setpoint - heating
Object is visible if the individual setpoint preset has been set in the parameters.
This data item forms the 2-byte KNX object and can be received. It is relevant for absolute
setpoint management. When a setpoint for an operating mode is received,
setpoint is automatically enabled.
30
Frost setpoint - heating
Object is always visible if the individual setpoint preset has been set in the parameters.
This data item forms the 2-byte KNX object and can be received. It is relevant for absolute
and relative setpoint management. When a setpoint for an operating mode is received,
setpoint is automatically enabled.
58 Commissioning | MYLOS
Building Automation
®
Commissioning
Adjustment
2 byte EIS1 DPT 9.001
Adjustment
2 byte EIS1 DPT 9.001
Adjustment
1 bit EIS1 DPT 1.001
Adjustment
2 byte EIS1 DPT 9.001
Adjustment
1 byte / 1 bit
Adjustment
2 byte EIS1 DPT 9.001
Adjustment
2 byte EIS1 DPT 9.001
Adjustment
2 byte EIS1 DPT 9.001
Adjustment
2 byte EIS1 DPT 9.001
C,R,T
C,R,T
C,W
C,W,T
C,R,T
C,R,W
C,R,W
C,R,W
C,R,W