Adjustment - ABB 2CSYK1201C Product Manual

Mylos knx
Table of Contents

Advertisement

MYLOS
Building Automation
®
6.3.3

Adjustment

No.
Function
9
Temperature sending
This data item forms the 2-byte object of KNX for the current temperature. The temperature is
measured in the „temperature sensor" application and can be weighted with an external input
temperature (object input for external current temperature). It can be sent only.
Must be cyclic and be able to send on change.
10
Heating status
This data item acts as an output and provides information on whether the ehating output is
currently enabled (including in the switched-off phases of a PWM cycle). This information
can be useful for visualisation.
11
High additional heat. adj.
This data item forms the 1-byte or 1-bit KNX object and can be sent only. This object represents the control value
for the additional heating stage (switching or quasi-continuous).
12
Cooling status
This data item acts as an output and provides information on whether the cooling output is
currently enabled (including in the switched-off phases of a PWM cycle). This information
can be useful for visualisation.
13
High heat. adj. (switching)
2 channel (4-pipe system)
This data item forms the 1-byte or 1-bit KNX object and can be sent only. This object is
the control value for heating. In fan coil systems with only one output channel it is the
„heating/cooling" object in which the internal allocation is controlled by the external operating
mode switching (see index 6).
When acting as a branch the control value is received via this object.
14
High cool. adj. (switching)
This data item forms the 1-byte or 1-bit KNX object and can be sent only. This object is
the control value for cooling.
This object is used with 2 channels (4-pipe system) only.
When acting as a branch the control value is received via this object.
Commissioning
Object name
Type of datum
Adjustment
2 byte EIS1 DPT 9.001
Adjustment
1 bit EIS1 DPT 1.001
Adjustment
1 byte / 1 bit
Adjustment
1 bit EIS1 DPT 1.001
Adjustment
1 bit EIS1 DPT 1.001 /
1 byte EIS1 DPT 5.001
Adjustment
1 bit EIS1 DPT 1.001 /
1 byte EIS1 DPT 5.001
Flags
C,R,T
C,R,W,T
C,R,T
C,R,T
C,R,T
C,R,T