Technical Specifications For The Analog Outputs - Siemens SIMATIC SM 335 Manual

High-speed analog input/output module for the simatic s7-300
Hide thumbs Also See for SIMATIC SM 335:
Table of Contents

Advertisement

Characteristics and Technical Specifications of the SM 335
1.5.3

Technical specifications for the analog outputs

Table 1-4
Resolution (incl. overrange)
" 10 V
From 0 to 10 V
Conversion time in ms
Setting time
For resistive load
For capacitive load
For inductive load
Injection of substitute values
Crosstalk between outputs
Operational limit (over entire temperature
range, based on output range)
Basic error
(operational limit at 25_C, based on output range)
Temperature drift
(based on output range)
Linearity error (based on output range)
Repeatability
(in steady state at 25 _C, based on output range)
Output ripple (based on output range)
Output range (rated values)
Burden resistance
For voltage outputs
For capacitive load
For inductive load
Voltage output
Short-circuit protection
Short-circuit current
Connection of actuators
For voltage output
– 2-wire connection
– 4-wire connection (measuring circuit)
1-10
Technical specifications for the analog outputs
Analog value formation for the outputs
Noise suppression and error limits for the outputs
Actuator Selection Data
SM 335 – High-Speed Analog Input/Output Module for the SIMATIC S7-300
11 bits + sign
12 bits (+ sign)
Max. 800
t 0.1 ms
v 3.3 ms
t 0.5 ms
Yes
–40 dB
0.5%
0.2%
0.02%/K
" 0.05%
" 0.05%
" 0.05%
" 10 V
From 0 to 10 V
Min. 3 kW
Max. 1 mF
Max. 1 mH
Yes
Max. 8 mA
Possible
Not possible
6ES7 335-7HG00-8BA1

Hide quick links:

Advertisement

Table of Contents
loading