INSTALLATION
Continued
Example
*Minimum 16 inches from Side Wall
Figure 6 - Minimum Clearance for Combustible to Wall
Mantel Clearances for Built-In Installation
If placing custom mantel above built-in firebox, you must meet the
minimum allowable clearance between mantel shelf and top of
firebox opening shown in Figure 7. These are the minimum allow-
able mantel clearances for a safe installation. Use larger clearances
wherever possible to minimize the heating of objects and materials
placed on the mantel.
CAUTION: Close screens before operation of
vent-free gas log heater. Do not allow the heater to
touch or extend beyond the fireplace screen.
If your installation does not meet the minimum clearances in
Figure 7, you must:
• raise the mantel to an acceptable height,
OR • remove the mantel.
Note :
All vertical measurements
are from top of fireplace
opening to bottom of mantel
shelf. All measurements
are in inches.
Facing material (above
firebox) may be of
combustible material,
including decorative
mantel ornaments.
Firebox
Wire-mesh
Screen
Figure 7 - Minimum Mantel Clearances for Built-In Installation
For more information, visit www.desatech.com
For more information, visit www.desatech.com
107331-01E
*
Mantel Shelf
10"
8"
6"
1 /2
2
"
For CGFB32C
13" 16"
19"
21"
Series circulating
louvered models
only
Supplied
Firebox Hood
Must Be Used
at All Times
Installation Clearances (Cont.)
Installing Blower Accessory
INSTALLING BLOWER ACCESSORY
You may install blower accessory GA3750 with conventional
installation (below) or with built-in installation (see Built-In Instal-
lation of Blower Accessory, page 8). To install blower accessory, see
instruction sheet included with the kit.
Conventional Installation of Blower Accessory
1. Install blower assembly per instruction sheet included in blower
accessory kit.
2.
Before replacing bottom of firebox, route blower power cord
through hole in support bracket in bottom of firebox and through
hole in side of firebox to grounded, three-prong 120 volt electri-
cal outlet (see Figure 8). Plug electrical cord into outlet.
3. Replace bottom of firebox.
NOTICE: A certified electrician must connect electri-
cal wiring to duplex outlet for built-in installation.
Follow all local codes. In absence of local codes,
follow the National Electrical Code, ANSI/NFPA 70
(Latest Edition) .
Blower
Blower Power Cord
Figure 8 - Routing Blower Accessory Power Cord for
Conventional Installation
INSTALLATION
7 7
Electrical
Outlet
Side
Opening
Support Bracket
Opening