7.1.5

Defining the initial position (0% or 100%)

4. Use a travel button (9) to move to the desired position.
5. Press the Accept button (2) or (4) to accept the position; if successful, the corresponding
LED flashes at a rate of 1 Hz. The other LED continues to flash at approx. 4 Hz.
7.1.6

Defining the second position (0% or 100%)

6. Use a button (9) to move to the second position.
7. To accept the position, press the Accept button (2) or (4). If successful, both LEDs(5) and
(10) flash at a rate of approx. 1 Hz.
7.1.7

Saving your settings

8. Press both Accept buttons (2 + 4) to accept the settings. The LEDs (5 + 10) stop flashing
after a short period of time and the adjustment process is completed.
9. If the range selected for the actuator is too small, both LEDs begin to flash again at 4 Hz and
the setup procedure must be repeated with a larger value (min. actuator travel).
(Information regarding actuator travel on the model plate)
42/68-830-EN
Commissioning and service field (ISF)
EBN853, EBN861 (Contrac)