AC Power For Business-Critical Continuity™ Liebert Battery System ® ™ Installation Manual...
Page 2
United States, call 1-800-LIEBERT (1-800-543-2378). Liebert Services offers a complete range of startup services, repair services, preventive maintenance plans and service contracts. For repair or maintenance service outside the 48 contiguous United States, contact Liebert Services, if available in your area.
This manual contains important instructions that should be followed during installation of your Liebert NXL Battery Cabinet and accessories. Read this manual thoroughly, paying special attention to the sections that apply to your installation, before working with the battery system. Retain this manual for use by installing personnel.
Page 8
Operation of this unit in a residential area may cause harmful interference that the user must correct at his own expense. ® ™ Liebert Battery System...
This following section describes the requirements that must be taken into account when planning the positioning and cabling of the Liebert NXL battery equipment. This chapter is a guide to general procedures and practices that should be observed by the installing engineer.
1.4.2 Clearances Liebert NXL has no ventilation grilles at either side or at the rear of the battery system equipment. Clearance around the front of the equipment should be sufficient to enable free passage of personnel with the doors fully opened. It is important to leave a distance of 24" (610mm) between the top of the cabinet and the ceiling of the room in which it is installed to permit adequate circulation of air coming out of the unit and for service access.
NSTALLATION Safety Special care should be taken when working with the batteries associated with the Liebert NXL Battery System equipment. When all the cells are connected together, the battery terminal voltage will exceed 400V and is potentially lethal. A primary safety consideration is to install the battery equipment in an isolated area, accessible only to properly trained and qualified maintenance personnel.
Battery cabinets connected, attached to UPS Additional Liebert Liebert Liebert Battery Battery Cabinet Cabinet If the Liebert NXL UPS is 500kVA to 750kVA, battery cabinets must be attached to the left side of the UPS. Additional Liebert Liebert Liebert Battery...
Battery Installation Figure 4 Stand-alone battery cabinets, detached from UPS Additional Stand- Liebert Liebert Liebert Alone Junction Battery Battery Cabinet Cabinet Cabinet Maximum of eight battery cabinets. The junction cabinet provides sufficient conduit landing space and is required for all systems in this configuration.
2.4.3 Attached/Detached System For battery cabinets that are connecting to a Liebert NXL UPS, (see Figure 2), cables will run from the positive and negative busbars of the adjacent battery cabinet to the positive and negative DC connections of UPS. For battery cabinets that are connecting to a Liebert NXL Junction Cabinet (see Figure 3), busbars will be connected from the positive and negative busbars of the adjacent battery cabinet to the positive and negative DC connections of Junction Cabinet.
Wiring external interface board in UPS to battery interface board in battery cabinet Detail A TB1154A EXT BATT External Interface Board (in UPS) Detail A TB1154A Battery Interface Board (in Battery Cabinet) Detail B TB1154 Detail B TB1154 ® ™ Liebert Battery System...
Network Power Liebert Services will set the ® jumpers on the EIB and the BIB. If another battery cabinet is added to the system after commissioning, it is imperative that Liebert Services reset the jumpers on the EIB board and the BIB board. ®...
External Battery Room Temperature Sensor—Optional For systems that do not use Liebert NXL Battery Cabinets, an optional temperature sensor can be installed to monitor the ambient room temperature. This sensor is connected to the BIB board (see Figure 7). This sensor will allow the Liebert NXL UPS to perform temperature compensation charging.
Installation Drawings Figure 9 Main components, Liebert Top-Terminal Battery Cabinet Negative Battery Bus Positive Battery Bus High Voltage Control Cable Trough Low Voltage Control Cable Trough Location for Optional Alber Monitoring Equipment Battery Service Tray Battery Breaker Battery Battery Service...
Negative Low Voltage Battery Bus Control Cable Trough Location for Optional Alber Monitoring Equipment Front Battery Battery Breaker Typ. Battery Typ. Battery Interface Board (BIB) Ground Bus Right Side View With Panels Removed Front View ® ™ Liebert Battery System...
5. All wiring is to be in accordance with national and local electrical codes. 6. For cabinets ordered as stand-alone, the negative and positive terminal bus does not extend to full width of battery cabinet. 7. 24" minimum clearance above unit is required for air exhaust and service. ® ™ Liebert Battery System...
Installation Drawings Figure 16 Liebert NXL Attached Junction Cabinet—terminal detail and outline drawing O .56 (14) Typ 1.75 (44) Typ Terminal Details 11.4 (290) Positive Bus Bottom 2 (51) Typ (178) O .56 (14) Typ 1.75 (44) Typ (112) Positive...
Installation Drawings Figure 17 Liebert NXL Battery Cabinet control wiring CAN cable to be run in trough closest to the front of the unit TROUGH 1- BRKR- NEG Thermistor (Optional) Optional Battery Voltage Sense Cable 3 4 5 NOTES TB1150...
TYPICA L GROUND STRA P INSTALLATION 2. Torque Values: M6: ( 5 Nm ) 40 IN-LB FOR BATTERY CABINE T TO M10: ( 14 Nm ) 120 IN-LB UPS OR ANCILLA RY CABINE T CONNECTIONS ® ™ Liebert Battery System...
UPS - External Interface Battery Cabinet - Battery CAN Control Cables Board (EIB) Interface Board (BIB) * This is used only for detached cabinets. If the cabinets are attached, use the grounding shown in Figure 19. ® ™ Liebert Battery System...
Installation Drawings Figure 22 Terminal details Liebert NXL UPS 250kVA - 400kVA to front terminal battery point-to-point wiring All power and control wiring is supplied if units are ordered as attached. For left-mounted installations, the DC cables will be routed along the interior rear of the UPS.
Installation Drawings Figure 25 Terminal details, Liebert NXL 500kVA UPS to Top-Terminal battery and Stand-Alone Junction Cabinet, point-to-point wiring Top View Ground Bus DC Input Stand-Alone Junction Cabinet Battery Cabinet UPS Left Side UPS Left Front (Part A) Rectifier (Part A)
Installation Drawings Figure 26 Terminal details Liebert NXL 500kVA to Top-Terminal battery point-to-point wiring UPS LEFT SIDE RECTIFIER (PART A) UPS LEFT FRONT (PART A) TOP VIEW NOTE: 1. All power and control wiring is supplied. 2. The units must be attached.
Installation Drawings Figure 27 Terminal details Liebert NXL UPS 500kVA to front terminal battery point-to-point wiring UPS LEFT SIDE RECTIFIER (PART A) UPS LEFT FRONT (PART A) TOP VIEW NOTE: 1. All power and control wiring is supplied. 2. The units must be attached.
Installation Drawings Figure 28 Liebert NXL terminal details UPS 625/750kVA to front terminal battery and Attached Junction Cabinet point-to-point wiring A1 & B1 - LH MOUNT A2 & B2 - RH MOUNT GROUND BUS DC INPUT UPS Left Side UPS Left Front (Part A)
Installation Drawings Figure 30 Terminal details, Liebert NXL 625/750kVA UPS to Top-Terminal battery and Attached Junction Cabinet, point-to-point wiring A2 and B2 - RH Mount A1 and B1 - LH Mount Top View DC (-) INPUT Ground DC Input UPS Left Side...
Installation Drawings Figure 31 Terminal details, Liebert NXL 625/750kVA UPS to Top-Terminal battery and Stand-Alone Junction Cabinet, point-to-point wiring Top View DC (-) Input GROUND DC INPUT UPS Left Side UPS Left Stand-Alone Rectifier (Part A) Front (Part A) Junction Cabinet...
UPS Cabinet Positive Bus Positive DC Power Junction Negative Bus UPS Cabinet Negative Bus Negative DC Power Junction Ground UPS Cabinet Ground Ground Battery Cabinet UPS External CAN Control Cables Battery Interface Board (BIB) Interface Board (EIB) ® ™ Liebert Battery System...
UPS Cabinet Positive Bus Positive DC Power Junction Negative Bus UPS Cabinet Negative Bus Negative DC Power Junction Ground UPS Cabinet Ground Ground Battery Cabinet Battery Interface Board (BIB) UPS External Interface Board (EIB) CAN Control Cables ® ™ Liebert Battery System...
Harness factory-installed. Wire Harness Verify transformer connection Prior to startup. See diagram below. V_OUT_A V_OUT_C NXL BATTERY CABINET UPS MODULE OUTPUT TOP TERMINALS BOTTOM TERMINALS FROM F5 FUSE IN BAT CAB FROM F4 FUSE IN BAT CAB XFMR CONNECTION DIAGRAM...
JAR 13 JAR 20 JAR 24 JAR 14 JAR 19 JAR 23 JAR 15 JAR 18 JAR 22 JAR 16 JAR 17 JAR 21 FRONT OF TRAY FRONT OF TRAY FRONT OF TRAY JAR (BATTERY) CONFIGURATION ® ™ Liebert Battery System...
12 11 10 JAR #21 JAR #19 JAR #12 JAR #10 15 14 13 18 17 16 Bottom of Cabinet CABLE JAR #18 JAR #17 JAR #16 JAR #15 JAR #14 JAR #13 INTERCONNECT DIAGRAM FRONT ® ™ Liebert Battery System...
Installation Drawings Figure 40 Busbar connection between Battery Cabinet and Attached Junction Cabinet Left-Side Busbar Connections Note: This connection is the same for top-terminal (12V) battery cabinets and front-terminal (16V) battery cabinets. Right-Side Busbar Connections ® ™ Liebert Battery System...
Alber battery monitoring option specifications Electrical Data Value Input Voltage 220-600VAC Input Current < 0.5A Frequency 60Hz Table 20 DC currents for Liebert NXL modules UPS Rating Max Battery Current at EOD 1241 1645 1850 2061 1100 1100 2860 ®...
(Nm) — 400 - 1200 Amps 300 (34) — Circuit Breakers with Compression Lugs (For Control Wiring) AWG Wire Size or Range lb-in (Nm) — #22 - #14 3.5 to 5.3 (0.4 to 0.6) — ® ™ Liebert Battery System...
Page 56
+39 049 9719 111 Fax: +39 049 5841 257 While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no Asia responsibility and disclaims all liability for damages resulting from use of 29/F, The Orient Square Building this information or for any errors or omissions.