Download Print this page

Mounting And Installation; Setting The Direction Of Rotation; Removing 1/2-Inch Shaft Guide For 3/8-In Or 5/8-In Shaft; Mounting Actuator To Damper Shaft - Siemens GDE131.1U Installation Instructions Manual

Openair electronic damper actuator gde/glb rotary non-spring return
Hide thumbs Also See for GDE131.1U:

Advertisement

Document No. 129-367
Installation Instructions
September 1, 2003
1
CLOCKWISE
TO OPEN
"0"
2
self adapt
0
self adapt
only for:
3
0
GDE16...1P
GLB16...1P
MODULATING
Figure 2. Setting the Direction of Rotation.
NOTE: For DIP switch setting options, see the
Technical Instructions EA GDE/GLB-1
(155-187P25).

Mounting and Installation

NOTE: The GDE/GLB actuator comes with a factory
installed 1/2-inch shaft guide. If shaft size is
1/2-inch, proceed with Figure 6.
When using a 3/8-inch shaft: Remove factory installed
1/2-inch guide. See Figure 3.
Figure 3. Removing 1/2-inch Ø shaft
guide for 3/8-in or 5/8-in shaft.
90
Figure 4. 3/8 Ø inch shaft, see Figure 1 Item f.
Page 2 of 6
COUNTER
CLOCKWISE
TO OPEN
2 '
self adapt
0
self adapt
only for:
3 '
0
GDE16...1P
GLB16...1P
MODULATING
f
Mounting GDE/GLB on
~ ~
3/8-inch
8...10 mm shafts
1. A 3/8-inch shaft adapter is provided in
actuator package.
2. Hold the shaft insert so that the raised tabs
are inserted last when placing the insert into
the back of the actuator.
3. Proceed to Figure 6.
When using a 5/8-inch shaft:
90
Figure 5. 5/8 Ø inch shaft.
1. Remove factory installed 1/2-inch guide. See
Figure 3.
2. Mount actuator to shaft per Figure 6.
Figure 6. Mounting Actuator to Damper Shaft.
4 mm
60-90 lb-in
(7-10 Nm)
Torque
b
4
Figure 7. Installing the Position Indicator (b).
Siemens Building Technologies, Inc.
2
1
3
5