Type EZR

Installation

All interventions on the equipment should only be performed by qualified and trained personnel.
WARNINg
!
The regulator is installed on horizontal pipeline.
Version with slam shut, the release relay is situated
towards the bottom (see schematic).
Installation according to EN12186 recommended.
Install according to direction of fluid flow (arrow).
When assembling with adjacent elements care
must be taken not to create pressure force on the
body and the assembling elements (bolts, O-rings,
flanges) should be compatible with the geometry and
working conditions of the equipment.
If the case arises a support must be used to avoid
pressure force on the body (a support can be installed
under the flanges).
Version with integral slam shut , connect the safety
manometric box (IS) to the impulse at 4D on a straight
run of the outlet pipe.
It is recommended to separate the slam shut impulse
line (IS) from that of the pilot (IP). Do not connect the
impulses on the lower generator line.
It is recommended to install an isolation valve and an
atmospheric valve, which can be useful for slam shut
tripping and verifications.
No modification should be made to the structure of
the equipment (drilling, grinding, soldering...).
8
B19
Figure 11. Type EZH Installation Configurations
WARNINg
!
It is recommended to install a servicing valve on the
outlet pipeline to facilitate adjustments and bleeding
off to the atmosphere.
Verify that the inlet side is protected by an
appropriate device(s) to avoid exceeding the limits of
utilization (PS, TS).
Verify that the limits of utilization correspond to the
appropriate operating conditions.
Version with integral slam shut, verify that the safety
manometric box (BMS) and spring correspond to the
appropriate operating conditions on the outlet side
of the regulator.
The equipment should not receive any type of shock,
especially the release relay.
The user should verify or carry out a protection
adapted to the environment.
Fire, seismic and lightening are not taken into
consideration in standard regulators. If required, a
special product selection and/or specific calculations
may be supplied according to specific requirements.
Version without integral slam shut, verify that a
pressure limiting device on the outlet side of the
regulator guarantees a pressure limit inferior or
equal to the pilot PS.