Mitsubishi Heavy Industries SRK60ZSX-S Technical Manual page 81

Inverter wall mounted type residential air-conditioners, split system, air to air heat pump type
Hide thumbs Also See for SRK60ZSX-S:
Table of Contents

Advertisement

Installation and wiring of remote control
Master/ slave setting when more than one remote controls are used
Screw
A maximum of two remote controls can be connected to one indoor unit (or one group of indoor units.)
Erectrical box
(Prepare on site)
Set SW1 to "Slave" for the slave remote control. It was factory set to "Master" for shipment.
Note: The setting "Remote control thermistor enabled" is only selectable with the master remote control in
The indication when power source is supplied
When power source is turned on, the following is displayed on the remote control until the
communication between the remote control and indoor unit settled.
M4 screw
2 (Prepare on site)
The thin part
At the same time, a mark or a number will be displayed for two seconds first.
Upper
This is the software's administration number of the remote control, not an error cord.
Lower case
Lower
When remote control cannot communicate with the indoor unit for half an hour, the below indication will
Upper
appear.
Check wiring of the indoor unit and the outdoor unit etc.
Lower case
Lower
Connect the remote control cord to the
terminal block.
Connect the terminal of remote control (X,Y)
with the terminal of indoor unit (X,Y).
(X and Y are no polarity)
Wiring route is as shown in the right diagram
depending on the pulling out direction.
The wiring inside the remote control case should be within 0.3mm
The sheath should be peeled off inside the remote control case.
The peeling-off length of each wire is as below.
Pulling out from upper left Pulling out from upper center
X wiring : 215mm
Y wiring : 195mm
Install the upper case as before so as not to catch up the remote control cord, and tighten with
the screws.
In case of exposing cord, fix the cord on the wall with cord clamp so as not to slack.
Wiring of remote control should use 0.3mm
Maximum prolongation of remote control wiring is 600 m.
If the prolongation is over 100m, change to the size below.
But, wiring in the remote control case should be under 0.5mm
the case according to wire connecting. Waterproof treatment is necessary at the wire connecting
section. Be careful about contact failure.
100 - 200m ......................... 0.5mm
Under 300m ....................... 0.75mm
Under 400m ....................... 1.25mm
Under 600m ....................... 2.0mm
Indoor units
Remote control cord (no polarity)
Remote control
Remote control
SW1 "Master"
SW1 "Slave"
the position where you want to check room temperature.
The air-conditioner operation follows the last operation of the remote control regardless of the
master/ slave setting of it.
Master remote control : "
Slave remote control : "
Upper
Board
Lower
Wiring
In case of pulling out from
upper left
2
X wiring : 170mm
Y wiring : 190mm
× 2 core wires or cables. (on-site configuration)
2
2
. Change the wire size outside of
× 2 cores
2
× 2 cores
2
× 2 cores
2
2
× 2 cores
Switch
Setting
M
Master remote control
SW1
S
Slave remote control
Master
Slave
"
"
The left mark is only an
example. Other marks may
appear.
80
-
-
Sheath
Sheath
Upper
Upper case
Upper case
Board
Lower
Wiring
In case of pulling out from
upper center
(recommended) to 0.5mm
2
.
The peeling-off length
of sheath
Contents
Upper
Board
Lower
'17 • SRK-T-203
The range of temperature setting
When shipped, the range of set temperat
Heating : 16 ~ 30°C (55 ~ 86°F)
Except heating (cooling, fan, dry, au
Upper limit and lower limit of
Upper limit setting: valid during heating
Lower limit setting: valid except heating
79°F).
When you set upper and lower limit by
1. When
TEMP RANGE SET, remo
If upper limit value is set
During heating, you cannot set the
If lower limit value is set
During operation mode except heat
2. When
TEMP RANGE SET, remo
If upper limit value is set
During heating, even if the value ex
But, the indication is the same as th
If lower limit value is set
During except heating, even if the va
But, the indication is the same as th
How to set upper and lower li
1. Stop the air-conditioner, and press
seconds .
The indication changes to "FUNCT
2. Press
button once, and chang
3. Press
(SET) button, and e
4. Select "UPPER LIMIT
5. Press
(SET) button to fix.
6. When "UPPER LIMIT
Indication: "
SET UP"
Select the upper limit value wit
(blinking)
Press
(SET) button to fi
After the fixed upper limit value
7. When "LOWER LIMIT
Indication: "
SET UP"
Select the lower limit value with
(blinking)
Press
(SET) button to fi
After the fixed lower limit value
8. Press ON/OFF button to finish.
It is possible to finish by pressing
ON/OFF button on the way, but
unfinished change of setting is
unavailable.
During setting, if you press
(RESET) button, you return to the
previous screen.
" or "LO
" is selec
" is selec