Reset conditions
40
3)
Reset conditions:
a)
a)
b)
b)
(ii)
Heating
1)
Operating conditions
(ii)
Heating
2)
Detail of operation
1)
Operating conditions:
3)
Reset conditions
2)
Detail of operation:
a)
3)
Reset conditions:
b)
a)
(r)
Refrigeration cycle system protection
b)
(i) Starting conditions
(r)
Refrigeration cycle system protection
1)
When 5 minutes have elapsed after the compressor ON or the completion of the defrost operation.
(i)
Starting conditions
2)
Other than the defrost operation.
1)
When A minutes have elapsed after the compressor ON or the completion of the defrost operation
3)
When, after satisfying the conditions of 1) and 2) above, the compressor speed, indoor temperature (Th1) and indoor
2)
Other than the defrost operation
heat exchanger temperature (Th2) have satisfied the conditions in the following table for 5 minutes.
3)
When, after satisfying the conditions of 1) and 2) above, the compressor speed, indoor air temperature (Th1) and indoor
heat exchanger temperature (Th2) have satisfied the conditions in the following table for 5 minutes:
Operation mode
Operation mode
Cooling
Heating
Cooling
Note (1) Except that the fan speed is HI in heating operation.
Heating
(ii) Contents of control
Note (1) Except that the fan speed is HI in heating operation and silent mode control.
1)
When the conditions of (i) above are satisfied , the compressor stops.
(ii)
Contents of control
2)
Error stop occurs when the compressor has stopped 3 times within 60 minutes.
1)
When the conditions of (i) above are satisfied, the compressor stops.
(iii) Reset condition
2)
Error stop occurs when the compressor has stopped 3 times within 60 minutes.
When the compressor has been turned OFF
(iii)
Reset condition
When the compressor has been turned OFF.
(t) Service valve (gas side) closing operation
(i)
Starting conditions
1)
Operation mode : Heating
2)
Compressor conditions : OFF
(ii)
Contents control
If the output current of inverter exceeds the specifications, it makes the compressor stopping.
(iii)
Anomalous stop control
1)
If the inverter output current value excceds the setting value within 80 seconds the compressor stops.
2)
After 3 minutes delay. the compressor restarts, but if this anomaly occurs 2 times within 20 minutes after
this initial detection.
Outdoor air temperature > 10˚C
Outdoor air temperature < = 10˚C
Lower limit fan speed
Outdoor temperature > 16˚C
Outdoor temperature < = 16˚C
24
8th (model71 : 7th)
5
Compressor speed (N)
A
Compressor speed (N)
50 N
< =
50 N
< =
(1)
5
40 N
40 N (TH2
8
(1)
60 N (TH2
ON
Outdoor fan
Outdoor fan
40
40
.
-2°C (models SRK50, 60 : 4°C)
3
2
at each 20 seconds
0°C (models SRK50, 60 : 6°C)
Indoor temperature (Th1)/
Indoor temperature (Th1)
Indoor heat exchanger temperature (Th2)
Room temperature (Th1)
10 Th1 40
< =
< =
< =
< =
0 Th1 40
10 Th1 40
0 Th1 40
50
-
-
'17 • SRK-T-203
Room temperature (Th1)/
Th1−4<Th2
Indoor heat exchanger temperature (Th2)
Th2<Th1+6
Th1−4<Th2
Th2<Th1+6
-
-