UPS USER MANUAL
F-16
LINE INTERACTIVE UPS
1KVA/1.5KVA/2KVA/3KVA

Advertisement

Table of Contents
loading

Summary of Contents for ION F-16

  • Page 1 UPS USER MANUAL F-16 LINE INTERACTIVE UPS 1KVA/1.5KVA/2KVA/3KVA...
  • Page 2: Save These Instructions

    SAVE THESE INSTRUCTIONS This user manual contains important instructions for the ION F-16 1000VA / 1500VA/ 2000VA / 3000VA series which should be followed for the installation and maintenance of the UPS and batteries. Please read all safety and operating instructions before operating the UPS.
  • Page 3: Table Of Contents

    CONTENTS 1. Introduction ············································································································ 1 2. Safety Warning ······································································································· 2 2.1 Description of Commonly Used Symbols ····························································· 3 3. Installation ·············································································································· 4 3.1 Inspection of Unit ······························································································· 4 3.2 Unpacking the Cabinet ······················································································· 4 3.3 UPS Setup ········································································································· 4 3.4 EBM Installation (Optional) ················································································· 9 3.5 UPS Initial Startup ····························································································...
  • Page 4: Introduction

    The series is convertible to rack and tower forms. It can be placed either in Rack 2U or Tower form. The front panel of the ION F-16 UPS includes LCD display and four control buttons which allow users to monitor, configure and control the unit.
  • Page 5: Safety Warning

    2. Safety Warning DANGER: This ION UPS contains high voltage. All repairs and service should be performed by authorised service personnel only. There are no user serviceable parts inside the UPS. WARNING: This ION UPS contains its own energy source (batteries).The UPS output may carry live voltage even when the UPS is not connected to an AC supply.
  • Page 6: Description Of Commonly Used Symbols

    Never dispose of batteries by incineration. Batteries may explode when exposed to flame. Following figure shows the basic internal circuit configuration of the ION UPS 2.1 Description of Commonly Used Symbols Some or all of the following notations in this manual may appear in your application process.
  • Page 7: Installation

    Setup and Rack-Mount Setup. Tower setup This series of ION UPS can be placed horizontally and vertically. For a tower configuration, stands have been provided to stabilise the UPS when it is positioned vertically. The UPS stand must be attached to the bottom of the...
  • Page 8 Use the following procedure to install ION UPS in its stands. 1. Slide the UPS down vertically and put the two stands at the end of the tower. 2. Place the UPS down between the two stands carefully.
  • Page 9 3. Pull out the LCD box and rotate it in a clockwise direction to 90 degrees and then push it back in the front panel.
  • Page 10 Rack-mount setup The series can be installed in 19 inch racks. Both the UPS and external battery enclosure need 2U of available rack space. Use the following procedure to install the UPS in a rack. 1. Align the mounting ears with screw holes on the side of the UPS and tighten the screw.
  • Page 11 3. Slide the UPS into the rack rail and lock it in the rack enclosure. 4. Tighten the screw, and the load can then be connected.
  • Page 12: Ebm Installation (Optional)

    3.4 EBM Installation (Optional) Connecting the EBM in Tower form: 1. Slide the UPS and EBM down vertically and place the two UPS stands with the extended part at the end of the tower. 2. Tighten the screw on the metal sheet to stabilise 3.
  • Page 13 4. Take off the front panel, and connect the battery terminal (A) from UPS to EBM terminal (B) as shown below. Users should remove the small gate (C) on side of the front panel to allow the outlet wire of the EBM to pass through the gate and then reassemble the front panel.
  • Page 14 2. Connect the earth line from UPS (port A) to EBM (port B) 3. Take off the LCD box, and unscrew the internal screws. Unscrew Unscrew...
  • Page 15 4. Take off the front panel, and connect the battery terminal (A) from UPS to EBM terminal (B) shown as below. Users need to remove the small gate (C) on side of the front panel to allow the outlet wire of the EBM to pass through the gate and then reassemble front panel.
  • Page 16 Connecting multiple EBMs in Tower form 1. Connect Earth line between UPS and the first EBM, then connect the Earth Line between the first EBM and the second EBM. 2. Take off the front panel, and connect the battery terminal (A) from UPS to EBM terminal (B) shown as below, then connect the battery terminal (D) from the first EBM to the battery terminal (E) from the second EBM.
  • Page 17 Connecting Multiple EBMs in rack form 1. Connect Earth line between UPS and the first EBM, then connect the Earth Line between the first EBM and the second EBM. 2. Take off the front panel, and connect the battery terminal (A) from UPS to EBM terminal (B) shown as below, then connect the battery terminal (D) from the first EBM to the battery terminal (E) from the second EBM.
  • Page 18: Ups Initial Startup

    3.5 UPS Initial Start-up To start up the ION UPS: 1. Verify that the internal batteries are connected. If optional EBMs are installed, verify that the EBMs are connected to the UPS. 2. Plug the equipment to be protected onto the UPS, but do not turn on protected equipment.
  • Page 19: Operation

    4. Operation 4.1 Display Panel This ION UPS has a four-button graphical LCD with dual colour backlight. Standard back-light is used to light up the display with black text and a blue background. When the UPS has a critical alarm, the backlight changes the background to red.
  • Page 20 The following table describes the functions of the LCD control buttons. Table2. Description of control button Control Switch Function Button --To turn on/off the UPS Press and hold the button for at least 3 seconds. --To release the UPS from faulty mode ON/OFF Cut off input power and then press and hold the button...
  • Page 21 LCD display functions: The following table describes the functions of the LCD display. Table3. Description of LCD display function Description Function Input frequency and Indicates the value of input frequency and voltage voltage Light is on when the UPS has input power. Input plug indicator Output frequency and Indicates the value of output frequency and...
  • Page 22 UPS Status Display String Description: The following table shows the description of the LCD display string: Table4. UPS Status Display String LCD Display String Description STbY UPS is on Standby mode IPVL Input voltage is too low IPVH Input voltage is too high IPFL Input frequency is too low IPFH...
  • Page 23: Operating Mode

    [000]=Disable [001]=Enable Automatic restart [000]=Disable [001]=Enable Green function [000]=Disable [001]=Enable Buzzer control [000]=Turn off [001]=Turn on Load segment 1 [000]=Turn off [001]=Turn on Load segment 2 4.2 Operating Mode Normal range mode: Under Input mode, the UPS accepts AC input voltage range for +/-20%.
  • Page 24: Configuring Ups For Ebm Numbers

    3. Enter settings item: When the LCD display “LS1” or “LS2”, press the enter button for 1 second to enter the setting item and the settings string will flash. 4. Select setting value: Press the Select button to select the settings value. Select the value [001] or [000] to set the desired load segment ON or OFF.
  • Page 25: Communication Port

    5. Communication Port 5.1 RS-232 and USB Communication Ports To establish communication between the UPS and a computer, connect your computer to one of the UPS communication ports using an appropriate communication cable. When the communication cable is installed, power management software will exchange data with the UPS.
  • Page 26: Network Management Card (Optional)

    Caution: The EPO must not be connected to any utility connected circuits. Reinforced insulation to the utility is required. The EPO Switch must have a minimum rating of 24Vdc and 20mA and a dedicated latching-type switch not tied into any other circuit. The EPO signal must remain active for at least 20 minutes for proper operation EPO Connections Wire Function...
  • Page 27: Ups Maintenance

    6. UPS Maintenance 6.1 UPS and Battery Care For the best preventive maintenance, keep the area around the UPS clean and dust-free. If the atmosphere is dusty, clean the outside of the system with a vacuum cleaner. For long battery life, keep the UPS at an ambient temperature of 25° C (77° F) 6.2 Storing the UPS and Batteries If you intend to store the UPS for a long period, recharge the battery every 6 months by connecting the UPS to utility power.
  • Page 28: Replacing Ups Internal Batteries

    which is harmful to skin and eyes. Note: If you are not qualified service personnel, do not attempt to open the battery cabin. Contact your local dealer or distributor immediately. 6.4 Replacing UPS Internal Batteries Follow the steps and Charts as below to replace batteries: 1.
  • Page 29 4. Remove the right inner battery bracket. 5. Pull the battery pack out onto flat area. 6. Install new battery pack into UPS. 7. Screw up the battery bracket and reconnect the battery cable A and B 8. Re-install the front panel back to UPS.
  • Page 30: Testing New Batteries

    6.5 Testing New Batteries For a battery test: Check that the batteries are fully charged. The UPS is in Normal mode with no active alarms. Do not take on/off the load. To test batteries: 1. Connect the UPS to utility power for at least 48 hours to charge the batteries. 2.
  • Page 31: Specification

    7. Specification 7.1 Specification Table7. Electrical Specification 1000 1500 2000 3000 Model 1000S 1500S 2000S 3000S Capacity Watt 900W 1350W 1800W 2700W Input voltage range 161-276VAC Input 50/60Hz ±5Hz for Normal Mode Frequency range 40-70Hz for Generator Mode Voltage 220/230/240VAC Voltage Regulation ±5% (Batt.
  • Page 32 Table8. Indicators and Audible alarm AC Mode NORM---normal mode Backup Mode Show “bATT” and sounding every 4 seconds Load/Battery Level LCD showing Indicator UPS Fault LCD show red screen and “ **** ” Overload LCD show red screen and “ OVLD ” Low Battery LCD show red screen and “...
  • Page 33: Rear Panels

    7.2 Rear Panels The UPS rear panel description table and pictures are shown as below: Function(1000VA &1500VA) AC Output Modem/Network Surge Protection SNMP Port AC Input RS232 / Dry-Contact Communication Port USB Port Earth Line Port INTE RFACE OP TION RS232 E PO 1000VA &1500VA Standard &...
  • Page 34 I N T E R F A C E O P T I O N C T I P R O L E P R K / N E T R S 2 3 2 U S B E P O 2000VA Standard model rear panel I N T E R F A C E O P T I O N I O N...
  • Page 35 The EBM rear panel description table and picture are shown as below: 36V &72V EBM) Function( Earth Line Port 36V &72V EBM rear panel...
  • Page 36: Trouble Shooting

    8. Trouble Shooting 8.1 Audible Alarm Trouble Shooting Indication Cause Solution Sounding every 4 The UPS is on battery Check input voltage seconds mode Sounding every The battery voltage is Save your work and turn off your Second and “bATL” on equipment screen Sounding every...
  • Page 37: Software Installation

    9. Software Installation Winpower is UPS monitoring software, featuring user-friendly interface to monitor and control of your UPS. This software provides power protection for your computer system during a power failure. With this software, users can monitor their UPS status on their LAN. Furthermore, a UPS can provide security protection for more than one computer on the same LAN at the same time, shutting down system in security, saving application data and shutting down the UPS if power fails.