Figure 6-310
6.45.4.14
Closing Indication and Close Command
After the expiration of the dead time, the Automatic reclosing function will be in the closing state.
The closing state can depend on the following influences, see
•
through a synchrocheck if the circuit breaker was opened during the 3-pole dead time
•
Through the readiness of the circuit breaker signaled through the binary input
•
Through a binary input for delaying the close command (
The
Close cmd. indication is a requirement for the assignment of the actual close command to the
circuit breaker.
The mentioned criteria must not be fulfilled directly after expiration of the dead time. If a dead-time prolonga-
tion is set, the mentioned criteria will be checked during the prolongation. With the release of the closing indi-
cation, the automatic reclosing function will switch to the reclaim time state.
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Cyclic Automatic Reclosing Function - Logic of Evolving-Fault Detection
Protection and Automation Functions
6.45 Automatic Reclosing Function
Figure
6-311:
>Delay close cmd. )