System Functions
3.5 Protection Communication
The Connection via parameter is used to set the bit rate required for the protection interface. Different
discrete values can be entered depending on the means of communication (see following table).
Table 3-13
Means of Communication
Fiber-optic direct connection
CC-XG-512 communication converter
CC-XG-128 communication converter
CC-XG-64 communication converter
Repeater 512 communication converter
CC-CC-128 Communication converter
CC-2M-512 Communication converter
Multiplexer with C37.94 interface
Other (freely adjustable bit rates for a direct
connection for special applications)
3.5.2.7

Routing Information in DIGSI 5

Protection communications of the same type form a topology.
For more information on this, see chapter
A data bar is exchanged between the devices of a topology connected via protection communication. This can
be written into or read from by the devices. This can be used for exchanging various signals between the
devices. In this case, each signal demands a certain number of data fields.
[dwdatenl-100113-01.tif, 1, en_US]
Figure 3-57
The data bar is divided into 3 priorities, which also have different transmission rates and data volumes.
The following basic principle applies for all messages: Only pure data contents are transmitted. The quality (for
example,
Valid ) is not automatically transmitted as well. If you want to transmit the quality as well (for
example, for further processing of GOOSE messages), the quality must be transmitted separately (for example,
by using CFC). If a signal that has a test flag is transmitted (because its function is in test mode, for example),
all signals are provided with a test flag on the receiving side. If the connection is broken, all received signals
are flagged with the quality
112
Means of Communication
3.5.2.3 Function
Data Bar Exchanged Between Devices
Invalid . If desired, the value can also be set to a secure state after a selectable
See
Setting Value
Figure 3-4
fiber optic
4
to
Figure 3-4
7
Figure 3-4
CCXG 512 kBit/s
8
Figure 3-4
CCXG 128 kBit/s
8
Figure 3-4
CCXG 64 kBit/s
8
Figure 3-5
repeater 512 kBit/s
1
Figure 3-5
CCPW 128 kBit/s
0
Figure 3-4
CC2M 512 kBit/s
9
Figure 3-5
C37.94 1 * 64 kBit/s
2
C37.94 2 * 64 kBit/s
C37.94 8 * 64 kBit/s
64 kBit/s
128 kBit/s
512 kBit/s
2048 kBit/s
Description.
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Bit Rate
2 MBit/s
512 kBit/s
128 kBit/s
64 kBit/s
512 kBit/s
128 kBit/s
512 kBit/s
64 kBit/s
128 kBit/s
512 kBit/s
64 kBit/s
128 kBit/s
512 kBit/s
2048 kBit/s