Connecting The Grounding Conductor; Circuit Diagram In The Terminal Box Cover; Terminal Designation - Siemens SIMOTICS XP 1MD4 Operating Instructions And Installation Instructions

Induction motor
Table of Contents

Advertisement

Working on terminal boxes of the "Ex e" type of protection with undrilled cable entry plate
This can result in death, serious injury or material damage.
Ensure that the cable entry plate is still strong enough after drilling the threads.
6.2.3

Connecting the grounding conductor

The cross-section of the machine grounding conductor must comply with the installation
regulations and also with IEC / EN 60204-1.
Table 6-1
A terminal strip for grounding is fitted either on the stator casing or on the flanged endshield,
depending on the frame size. The grounding point is marked.
The terminal strip is suitable for connecting stranded cables with cable lugs or connecting flat
straps. In addition, all motors have a PE terminal within the terminal box.
When connecting up the grounding conductor, ensure that the contact surface of the
connection is bare and protected against corrosion using a suitable agent, e.g. with acid-free
Vaseline.
6.2.4

Circuit diagram in the terminal box cover

Data on the connection and connecting the motor winding can be found in the circuit diagram
in the cover of the terminal box.
6.2.5

Terminal designation

According to IEC / EN 60034‑8, the following basic definitions apply to the terminal
designations for 3-phase machines:
Table 6-2
1
x
SIMOTICS XP 1MD4/1MD5
Operating Instructions 05/2015
CAUTION
Determining the cross-section of the grounding conductor
External cable cross-section S
S ≤ 16 mm²
16 mm² < S ≤ 35 mm²
S > 35 mm²
Terminal designations using the 1U1-1 as an example
U
1
-
1 Designation
Index for pole assignment for pole-changing machines where applicable. A lower
index signifies a lower speed. Special case for split winding.
x
Phase designation U, V, W
Cross-section of the grounding conductor [mm²]
S
16 mm²
S/2
Electrical connection
6.2 Connecting
53

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simotics xp 1md5

Table of Contents