Start-up and control with I/O

What this chapter contains

The chapter instructs how to:
• do the start-up
• start, stop, change the direction of rotation and adjust the speed of the motor
through the I/O interface.
Using the control panel to do these tasks is explained briefly in this chapter. For
details on how to use the control panel, please refer to chapter
on page 45.

How to start up the drive

Before you start, ensure that you have the motor nameplate data on hand.
The start-up may only be carried out by a qualified electrician.
The safety instructions given in chapter
procedure.
The drive will start up automatically if the external run command is on.
Check the installation. See the checklist in chapter
Check that the starting of the motor does not cause any danger.
De-couple the driven machine if there is a risk of damage in case of incorrect direction of
rotation.
Apply input power.
The panel goes to the Output mode.
Select the application macro (parameter 9902).
The default value 1 (ABB STANDARD) is suitable in most cases.
The general parameter setting procedure in the Short Parameter mode is
described below. You find more detailed instructions on setting parameters
on page 53.
The general parameter setting procedure in the Short Parameter mode:
1. To go to the Main menu, press
otherwise press
SAFETY
POWER-UP
ENTRY OF START-UP DATA
if the bottom line shows OUTPUT;
repeatedly until you see MENU at the bottom.
Safety
must be followed during the start-up
Installation
checklist.
LOC
OUTPUT
LOC
LOC
Start-up and control with I/O
39
Control panel
starting
00
.
Hz
FWD
9902
s
PAR
FWD
rEF
MENU
FWD