Check-Out Procedures - Lennox CBA25UH Installation Instructions Manual

Merit series air handler units, multi-position air handlers
Hide thumbs Also See for CBA25UH:
Table of Contents

Advertisement

NOTE - Refer to wiring diagram located on the
unit
ance (table 2).
All air data measured external to unit with 1
inch non-pleated air filter in place.
All factory settings are medium speed.
All data given while air handler is operating
with a dry DX coil.
All downflow applications run on high speed
when utilizing electric heat.
TABLE 2. CBA25UH Blower Performance (3-Speed PSC) – 240V (CFM @ ESP. – in. W. C.)
Air Handler
Blower Speed
Model
Low (Red)
Med (Blue)
-018
High (Black)
Low (Red)
Med (Blue)
-024
High (Black)
Low (Red)
Med (Blue)
-030
High (Black)
Low (Red)
Med (Blue)
-036
High (Black)
Low (Red)
Med (Blue)
-042
High (Black)
Low (Red)
Med (Blue)
-048
High (Black)
Low (Red)
Med (Blue)
-060
High (Black)
• Blower Performance (CFM vs. ESP inches H
• Cooling speeds should not be reduced below factory setting.
• All units with electric heat approved at 0.5" maximum and medium blower speed minimum.
• All downflow applications run on high speed when utilizing electric heat.

Check-out Procedures

NOTE – Refer to outdoor unit installation instructions for sys-
tem start-up instructions and refrigerant charging instructions.
PRE-START-UP CHECKS
• Is the air handler properly and securely installed?
• If horizontally configured, is the unit sloped up to 5/8
inch toward drain lines?
• Will the unit be accessible for servicing?
• Has an auxiliary pan been provided under the unit with
separate drain for units installed above a finished ceil-
ing or in any installation where condensate overflow
could cause damage?
BLOWER RELAY
5
2
FIGURE 16. Changing Blower Speed
.10" WC
.20" WC
510
495
670
650
905
865
630
625
885
875
1130
1100
900
865
1075
1060
1240
1210
1075
1040
1300
1250
1510
1450
1325
1315
1490
1465
1820
1770
1775
1710
1995
1895
2070
1970
1675
1630
1965
1925
2140
2085
0)
2
• Have ALL unused drain pan ports been properly
• Has the condensate line been properly sized, run,
• Is the duct system correctly sized, run, sealed, and in-
• Have all cabinet openings and wiring been sealed?
• Is the indoor coil factory-installed TXV properly sized for
• Have all unused parts and packaging been disposed
• Is the filter clean, in place, and of adequate size?
Page 16
BLOWER RELAY
HARNESS
BLUE (MED)
4-PIN
BLOWER CONNECTOR
.30" WC
475
630
820
615
850
1070
830
1030
1170
1000
1205
1390
1300
1440
1690
1645
1800
1850
1580
1875
2000
plugged?
trapped, pitched, and tested?
sulated?
the outdoor unit being used?
of?
PLASTIC CAPS
RED (L0)
BLACK (HI)
YELLOW (COM)
.40" WC
.50" WC
420
325
595
505
770
705
610
580
820
780
1010
950
780
740
985
940
1135
1085
950
900
1145
1085
1320
1245
1275
1225
1395
1315
1600
1500
1565
1470
1685
1560
1719
1595
1520
1450
1800
1695
1895
1795