Maintenance Of Plate Type Heat Exchanger - LG ARWB80LA2 Installation Manual

Multi v water ii system, outside unit r410a, arwb series
Table of Contents

Advertisement

How to Cope with Abnormal Test Run
Item
Phenomenon
When connecting the flow switch,
heat-sourced water doesn't flow or
CH24
the amount of its flow lacks due to
the checked error related to heat-
sourced water.
Heat water not supplied or flow rate
Whether
CH32
is insufficient (During air conditioning)
heat water
is supplied
Heat water not supplied or flow rate
CH34
is insufficient
Heat water not supplied or flow
CH180
rate is insufficient (During heating)
❈ When CH24 or CH180 error occurs during the test operation of the heater, the inside of the panel heat exchanger may be
partially frozen and therefore, be sure to get rid of its cause and then, re-operate the device.
(The root cause of partial freezing: The lack of flow of heat-sourced water, suspension of water, lack of cooling medium,
infiltration of foreign substance inside of panel heat exchanger )

Maintenance of plate type heat exchanger

As the scales are created in the panel heat exchanger, its efficiency may decrease or damage may occur due to winter-sowing due to the decrease in its
flow.
Due to this reason, regular maintenance is necessary so that the scales shouldn't be created.
1. Before the season of use, check below points.(Once a year)
1) inspection on water quality to check if this is within the standard condition.
2) Clean the strainer.
3) Check if the flow is appropriate.
4) Check if the operation environment is appropriate.(Pressure, flow, output temperature)
2. Below procedure should be abided by in order to clean the panel heat exchanger. (Once every 5 years)
1) Check if the service port is equipped with the water pipe in order to clean the chemical solution.
5% diluted formic acid, citric acid, oxalic acid, acetate acid, phosphoric acid and etc. are appropriate for the chemical solution for wiping out the
scales.(Hydrochloric acid, sulphuric acid, nitric acid and etc. shouldn't be used due to its corrosion.)
2) Be sure to check if the gate valve of inflow/outflow pipe and the valve for outflow pipe are properly closed when cleaning.
3) Connect the water pipe for cleaning with the chemical solvent through the service plug of the pipe and fill up the panel heat exchanger with
50°C~60°C of cleaning solvent and circulate it with the pump for 2~5 hours. The circulation time may depend on the temperature of the cleaning sol-
vent or the creation of the scales. Therefore, observe change in the color of the chemical solvent to set the circulation time for removing the scales.
4) After the circulation of the solvent, extract the solvent inside of the panel heat exchanger and fill up 1~2% of NaOH or NaHCO
for 15~20 minutes to neutralize the heat exchanger.
5) Once the neutralization is completed, clean the inside of the panel heat exchanger with clean water.
Measure the water Ph to check if the chemical solvent is properly removed or not.
6) When using a different kind of chemical solvent in the market, be sure to check if there is any corrosive action to stainless or copper in advance or not.
7) For details on the cleaning chemical solvent, be sure to consult the specialists of the related corporation.
3. After cleaning, operate the device to see if it works properly once again.
Cause
Check whether the heat source water supply pump is operating.
Check whether the heat source water supply pipe is clogged.
(Clean strainer, valve locked, valve issue, air trapped etc.)
Check whether the flow switch is normal condition.
(Flow switch problem, arbitrary control, disconnection etc.)
Check whether heat source water supply pump is operating.
Check whether the heat source water supply pipe is clogged.
(Clean strainer, valve locked, valve issue, air trapped etc.)
Check whether heat source water supply pump is operating.
Check whether the heat source water supply pipe is clogged.
(Clean strainer, valve locked, valve issue, air trapped etc.)
Check whether heat source water supply pump is operating.
Check whether the heat source water supply pipe is clogged.
(Clean strainer, valve locked, valve issue, air trapped etc.)
Gate valve(locked)
Gate valve(locked)
Service plug
Water-cooling
type multi V
Strainer
Outflow water
valve(locked)
[Cleaning the panel heat exchanger]
Checkpoint and resolution
Hose
Screening net
Pump
Installation Manual 75
Test Run
and then, circulate it
3