(2) Indoor unit setup method for priority indoor unit mode

The setting can be changed only when the system is at rest. (Be sure to turn
off the system prior to this operation.)
1
Push the
least 4 seconds. The display window will start flashing in a little
while.
Verify that the displayed CODE No. is 10.
• If the displayed CODE No. is not 10, press the
display and repeat the procedure from the beginning.
(Note that the system does not respond to remote controller operation
for about 1 minute after the
(In the case of group control, the indoor unit No. displayed first indicates
the header unit.)
2
Each time the
unit Nos. under group control is displayed in turn. Select
the indoor unit whose setting is to be changed.
The fan and flap of the selected indoor unit then come on, so
that the position of this unit can be confirmed.
3
Use the
4
Use the
Priority set 0001
5
Push the
The setup is finished when the display changes from flashing to steady.
6
Upon finishing the setup, push the
finalizes the setting.)
When the
system returns to normal off state.
(Note that the system does not respond to remote controller
operation for about 1 minute after the
NOTE
Priority can be given to only one indoor unit. If more than one indoor unit is accidentally set to priority, an error code
(L5 or L6: Duplicated indoor unit priority setting) will be displayed.
All units displaying L5 have been set to 0001 (priority). Keep the unit to which priority should be given as it is, and
change the value back to 0000 (no priority) for all the rest.
Error code
Downloaded from
www.Manualslib.com
+
+
buttons simultaneously and hold for at
button is pushed.)
UNIT LOUVER
button is pushed, one of the indoor
button to select the CODE No. 04.
button to select the SET DATA 0001.
No priority set 0000
button.
button is pushed, the display goes blank, and the
Description
Duplicated indoor unit priority setting (The unit is set to 0001.)
Duplicated indoor unit priority setting (The unit is set to 0000.)
manuals search engine
button to erase the
button. (This
button is pushed.)
108
TEMP.
ON / OFF
TIMER SET
FAN
MODE
TIME
SAVE
VENT
FILTER
RESET
TEST
SET
CL
SWING/FIX
UNIT LOUVER
5
4
3
6
1
2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mmy-map0804ht8zg-eMmy-map0804ht8z-eMmy-map1004ht8-eMmy-map1004ht8zg-eMmy-map1204ht8-eMmy-map1204ht8z-e ... Show all

Table of Contents