Technical Specification - Liebert Hinet 10kVA User Manual

Hinet ups system 10-30 kva 3x1
Table of Contents

Advertisement

Hinet UPS User Manual

6 Technical Specification

Input Data
Nominal Input Voltage
Input Voltage Range
Nominal Input Frequency
Input Frequency Range
Maximum Input Current at Nominal Input Voltage
Input Current Harmonic Distortion (THD)
Input Power Factor
Output Data
Nominal Output Voltage
Output Voltage Adjustment Range
Output Voltage Stability
Static Balanced Load
Dynamic 50% Load Step
Dynamic 100% Load Step
Output Voltage Transient Recovery Time
Output Voltage Distortion (THD)
Linear Load
Non Linear Load (100% 3:1 Crest Factor Load)
Nominal Output Frequency
Output Frequency Regulation
Synchronised With Input
Free Running
Maximum Slew Rate
Nominal Output Power Rating
kVA
kW
Output Nominal Power Factor
Overload Capability on Inverter (Load Will Transfer to
Static Bypass if Times are Exceeded)
Output Short Circuit Current
Maximum Load Crest Factor
10kVA
15kVA
380, 400, 415V selectable, 3 phase, neutral and earth
300 – 480Vac (330 – 480Vac full charging capability)
50 or 60Hz
40 – 70Hz
18.5A
25.3A
<28% (with THDI filter <10%)
0.95 (over specified load and voltage ranges)
220, 230, 240Vac selectable
Nominal ±5%
<30ms (to 3% RMS)
50 or 60Hz
±1% or ±4%, selectable
±0.005%
1Hz/sec
10
15
8
12
125% for 10 minutes, 150% for 10 seconds
200% of nominal current for 100ms
3:1 (at full load without derating)
(/01)
20kVA
30kVA
31.7A
45.0A
±1%
±3%
±5%
3%
5%
20
30
16
24
0.8
Page 25

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hinet 15kvaHinet 20kvaHinet 30kva

Table of Contents