Power Supply/Input/Output Specifications And Examples Of External Wiring - Mitsubishi Electric FX3UC-16MT/DSS Hardware Manual

Melsec-f fx3uc (d, ds, dss) series

Advertisement

Removal of the power cable
1) Turn the power supply OFF.
2) Pinch the power cable
connector "a" and disconnect
it in the direction of the arrow
(see figure on the right).
a
Press here
Power Cable types "A" and "B" are supplied with the main unit, while
type "C" is supplied with the FX
-EX, FX
-16EX-T, and
2NC
2NC
FX
/FX
series special function blocks.
2NC
3UC
Cable supplied
Type
Application
Model Length
with
FX
-MT/
3UC
FX
-
2NC
Power cable for main
1 m
D(SS),
A
100MP
unit
(3' 3")
FX
3UC
-16MR/
CB
D(S)-T
Input power cable for
FX
series input
FX
-
2NC
2NC
1 m
FX
-MT/D,
3UC
B
extension blocks and
100BP
(3' 3")
FX
-16MR/D-T
3UC
FX
/FX
series
CB
2NC
3UC
special function blocks
Input power crossover
FX
-EX,
2NC
cable for FX
FX
-16EX-T,
2NC
2NC
FX
-
2NC
series input extension
0.1 m
and
C
10BPC
blocks and FX
/
(3.93")
FX
/FX
2NC
2NC
B1
FX
series special
series special
3UC
function blocks
function blocks
The crossover cable (type "C") can skip up to 4 16-point output
blocks to connect units.
If more blocks should be skipped to supply power to an input block,
use cable type "B".
2.5
Connection to input/output connector
The input/output connectors of the Main units (Connector type)
conform to MIL-C-83503.
→ Refer to Chapter 4 for the I/O connector pin arrangement.
Input
X
1) Compliant connectors (commercially available connectors)
Use a 20-pin (1-key) socket connector conforming to MIL-C-
83503.
Confirm in advance that the connectors do not interfere with other
parts including connector covers.
2) Input/output cables (available from Mitsubishi)
Input/output cables with attached connectors are available.
Model
Length
Description
names
FX-16E-
5 m
General-purpose
500CAB-S
(16'4")
input/output cable
FX-16E-
1.5 m
150CAB
(4'11")
Cables for
connecting the
FX-16E-
3 m
FX Series
300CAB
(9'10")
3UC
terminal block
FX-16E-
5 m
with input/
500CAB
(16'4")
output
connectors.
FX-16E-
1.5 m
For terminal block
150CAB-R
(4'11")
connection, refer
FX-16E-
3 m
to FX
Series
3UC
300CAB-R
(9'10")
User's Manual -
Hardware Edition.
FX-16E-
5 m
500CAB-R
(16'4")
FX-A32E-
1.5 m
150CAB
(4'11")
Cables for
connecting the A
FX-A32E-
3 m
Series Model
300CAB
(9'10")
A6TBXY36
connector/
terminal block
FX-A32E-
5 m
conversion unit
and input/output
500CAB
(16'4")
connector type
3) Connectors for user-made input/output cables (available
from Mitsubishi)
Users should provide electric wires and a pressure bonding tool.
Model name and composition of
input/output connector
Our model name
Output
Y
by DDK Ltd.)
Solderless
FX
-I/O-
10-
2C
connector
CON for
piece
FRC2-
flat cable
set
A020-30S
Housing
HU-200S2-
FX
-I/O-
5-
2C
001
CON-S
piece
Solderless
for bulk wire
set
contact
HU-411S
Housing
HU-200S2-
FX
-I/O-
5-
Shape
2C
001
CON-SA
piece
Solderless
• Single wire
for bulk wire
set
contact
(Wire color: red)
HU-411SA
• PLC side:
A 20-pin connector
4) Certified connectors (commercially available connectors)
Connectors made by DDK Ltd. shown in item 3).
• Flat cables
2.6
Connection to input/output terminal block
(with tube)
• A 20-pin connector
2.6.1
Cable
at both ends
1) Applicable cable
Type
• Round multicore
Single wire
0.3 mm
cables
Double wire
• A 20-pin connector
0.3 mm
at both ends
2) Termination
Strip the coating of strand wire and twist the cable core before
• Flat cables (with tube)
connecting it, or strip the coating of single wire before connecting
• PLC side: Two 20-
it. An alternative connection is to use a ferrule with insulating
pin connectors in
sleeve.
16-point units.
<Reference>
• Terminal block side:
Manufacturer
A dedicated
connector
• One common
Phoenix Contact
AI 0.5-8WH
terminal covers 32
input/output
(
*
1) Old model name: CRIMPFOX ZA 3
terminals.
*
(
2) Old model name: CRIMPFOX UD 6
• Stranded wire/solid wire
Termination of
cable end
9 mm
(0.36")
When using a stick terminal with an insulating sleeve, choose a wire
with proper cable sheath referring to the above outside dimensions,
otherwise the wire cannot be inserted easily.
2.6.2
Tighten the terminals to a torque of 0.22 to 0.25 N•m.
Do not tighten terminal screws with a torque outside the above-
Applicable electric wire
mentioned range.
(UL-1061 are
Failure to do so may cause equipment failures or malfunctions.
recommended) and tool
Tool
Pressure
Details of
To tighten terminals, use a
Electric
bonding tool
part (made
purchased small-sized screwdriver
wire size
(made by
whose head is straight and is not
DDK Ltd.)
widened as shown in the right
AWG28
357J-4674D:
figure.
(0.1 mm
2
)
Main body
Note:
357J-4664N:
1.27 pitch,
Attachment
If the diameter of screwdriver grip is too small, tightening torque will
20-core
not be able to be achieved. To achieve the appropriate tightening
torque shown in the table above, use the following screwdriver or an
appropriate replacement (grip diameter approximately 25 mm
AWG22
(0.98")).
357J-5538
2
(0.3 mm
)
<Reference>
Phoenix Contact
AWG20
357J-13963
2
(0.5 mm
)
3.
DESIGN
PRECAUTIONS
• Make sure to have the following safety circuits outside of the
PLC to ensure safe system operation even during external
power supply problems or PLC failure.
Otherwise, malfunctions may cause serious accidents.
1) Most importantly, have the following: an emergency stop
Wire size
2
2
to 0.5 mm
(AWG22 to 20)
×
2
(AWG22)
2
2) Note that when the PLC CPU detects an error, such as a
Model
Caulking tool
3) Note that when an error occurs in a relay, triac or transistor
CRIMPFOX 6 (
*
1)
(or CRIMPFOX 6T-F (
*
2))
DESIGN
PRECAUTIONS
• Bar terminal with insulating sleeve
• Do not bundle the control line together with or lay it close to the
Insulating sleeve
Contact area
main circuit or power line. As a guideline, lay the control line at
(Crimp area)
least 100 mm (3.94") or more away from the main circuit or
power line.
Noise may cause malfunctions.
8 mm
(0.32")
• Install module so that excessive force will not be applied to
2.6 mm
peripheral device connectors, power connectors or input/output
(0.11")
14 mm(0.56")
connectors.
Failure to do so may result in wire damage/breakage or PLC
failure.
Tightening Torque
With
straight tip
0.4 mm
2.5 mm
(0.02")
(0.1")
Manufacturer
Model
×
SZS 0.4
2.5
Power supply/input/output specifications
and examples of external wiring
circuit, a protection circuit, an interlock circuit for opposite
movements (such as normal vs. reverse rotation), and an
interlock circuit (to prevent damage to the equipment at the
upper and lower positioning limits).
watchdog timer error, during self-diagnosis, all outputs are
turned off. Also, when an error that cannot be detected by
the PLC CPU occurs in an input/output control block,
output control may be disabled.
External circuits and mechanisms should be designed to
ensure safe machinery operation in such a case.
output device, the output could be held either on or off.
For output signals that may lead to serious accidents,
external circuits and mechanisms should be designed to
ensure safe machinery operation in such a case.