Terminal Mode; Printing Selected Information - Eaton Powerware 9315 UPS Powerware 9315 Installation And Operation Manual

500–750 kva
Hide thumbs Also See for Powerware 9315 UPS Powerware 9315:
Table of Contents

Advertisement

COMMUNICATION
12.4

Terminal Mode

12-6
EATON Powerware
In this mode, system events are continually logged through the serial port to the
device connected to the port. Port 2 operates by default in Terminal mode.
The Event History Log entries contain a time and date stamp and the alarm text
message. Terminal mode uses this format for printing alarm entries:
MMM DD
HH:MM:SS.hh
Symbol
MMM
DD
HH
MM
SS
hh
KYWD
::::
<CR>
<LF>
An alarm message is prefixed by the word CLEAR whenever an alarm is entered into
the Event History Log with a cleared status.
12.4.1

Printing Selected Information

NOTE To use a key combination, hold down the Control key and press the letter key.
If a port is operating in Terminal mode and is connected to a computer, use the
following key combinations at any time to print selected information:
[Ctrl]+[P]
Prints the entire log with a header
[Ctrl]+[M]
Prints the current system meters with a header
[Ctrl]+[A]
Prints all system information
[Ctrl]+[B]
Prints Battery Test Log
®
9315 UPS (500–750 kVA) Installation and Operation Manual
KYWD MESSAGE ::::
Description
Month (3 letters)
Day (2 digits)
Hour (2 digits)
Minute (2 digits)
Second (2 digits)
Hundredths of Second (2 digits)
Keyword (ALARM, NOTICE, COMMAND, or STATUS)
System Diagnostic Information
Carriage Return Character (ASCII 13)
Line Feed (ASCII 10)
S
164201244 Rev E www.powerware.com
<CR> <LF>