Product Specifications; Model Numbers; Ups System Input - Eaton Powerware 9315 UPS Powerware 9315 Installation And Operation Manual

500–750 kva
Hide thumbs Also See for Powerware 9315 UPS Powerware 9315:
Table of Contents

Advertisement

Chapter 14
Figure
14.1

Model Numbers

14.2

UPS System Input

EATON Powerware

Product Specifications

The following sections detail the input, output, environmental, and battery
specifications for the UPS.
The UPS systems are housed in free‐standing, double‐front cabinets with safety
shields behind the doors. The UPS systems are available in 50/60 Hz with various
output power ratings. Smaller models within a system may be upgraded in the field to
larger models:
System
Powerware 9315‐625
Powerware 9315‐750
Operating Input Voltage
(Nominal +10/–15%)
Operating Input Frequency
Range
Operating Input Current
Input Current Harmonic
Content
Power Walk‐In
Power Factor
Line Surges
®
9315 UPS (500–750 kVA) Installation and Operation Manual
Models
562, 500, 450, 400 kW
675, 600, 562, 500 kW
600 Vac for operation from 510 Vac to 660 Vac (60 Hz only)
480 Vac for operation from 408 Vac to 528 Vac (60 Hz only)
400 Vac for operation from 340 Vac to 440 Vac (50/60 Hz only)
"3 Hz of nominal (50 Hz or 60 Hz)
Battery Charge
125% of full load for overload + battery charge
Actual load + 25% of full load for battery charge with 0.8 pF
output units
115% of full load for overload + battery charge
Actual load + 15% of full load for battery charge with 0.9 pF
output units
Reduced for Generator
Adjustable, set to 102%
5% THD at full load (with input filter option installed)
Adjustable 3–60 second rectifier ramp‐up to full utility load
Minimum 0.85
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801‐4
S
164201244 Rev E www.powerware.com
Notes
50/60 Hz
60 Hz only
14-1