Samson 3374-10 Mounting And Operating Instructions page 86

3374 series electric actuator with positioner, revision 3
Table of Contents

Advertisement

Decommissioning and disassembly
Code Parameters
Characteristic
c71 Characteristic type
c72 User-defined characteristic
PID controller
c80 Operating point Y
c81 Set point
c82 Proportional-action coeffi-
cient KP
c83 Reset time Tn
c84 Derivative-action time Tv
Scaling of the set point for PID controller
c85 Unit
c86 Lower range value
c87 Upper range value
Process variable adjustment
c88 Lower limit of range
c89 Upper limit of range
Set point deviation
c90 Function
Actuator
c91 Customized key number
active
c92 Customized key number
c93 Backlight always on
c94 Key number is active
86
Setting range (select ESC to cancel)
LIN (linear)
EQUA (equal percentage)
INV (reverse equal percentage)
USER (user-defined)
User-defined
0 to 100 %
0
0.0 to 100.0 %
0.1 to 50.0
0 to 999 s
0 to 999 s
NONE (none)
PER (%)
CEL (°C)
BAR (bar)
–999 to 999
–999 to 999
Depending on c85 (see above)
Depending on c85 (see above)
0: Not inverted; 1: Inverted
NO
YES
0000 to 1999
NO
YES
NO
YES
WE
Section
Customer
LIN
9.12
9.12
0 %
8.4
50.0 %
8.4
1.0
8.4
20 s
8.4
0 s
8.4
PER
0
100
0
100
0
NO
7.4.1
0000
7.4.1
NO
8.2.2
NO
7.4
EB 8331-4 EN
data

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

3374-263374-113374-313374-363374-153374-21

Table of Contents