Dip Switch Information - LG THERMA V AHBW036H0 Installation Manual

Air-to-water heat pump
Hide thumbs Also See for THERMA V AHBW036H0:
Table of Contents

Advertisement

DIP switch information

• If you set Dip switch when power is on, the changed setting will not be applied immediately.
The changed setting will be enabled only when Power is reset or by pressing Reset button.
ON
8 7 6 5 4 3 2 1
OFF
Description
Reserved
Accessory installation
information
Emergency operation
Level.
External water pump
installation information.
Reserved
Thermostat installation
information.
CAUTION
1. "X" mark means dip switch must be off. Otherwise the function may not operates
correctly.
2. If each dip switch doesn't set correctly, unit will operate abnormally.
3. In case of proceeding test run, start after checking if all unit is off.
Setting
Please keep default setting (Not use central control)
Unit only
Unit + Sanitary water tank is installed.
Unit + Sanitary water tank +Solar thermal system is installed.
High temperature cycle
Low temperature cycle
External water pump is NOT installed.
External water pump is installed.
Please keep default setting (Not use unit electric heater)
Thermostat is NOT installed.
Thermostat is installed.
Default
System Set-Up
1
2
3
4
5
6
7
X
X X
X ●
● X
X
X
● X
X X X X X ● X X
Installation Manual 43
8
X

Hide quick links: