Fsl100 Specifications - Honeywell FSL100-IR3 Technical Handbook

Fsl100 series
Table of Contents

Advertisement

12 FSL100 Specifications

Power
Current Normal
Current In Alarm
Start Up Time
Alarm Output Setting
Connects to
End Of Line And Alarm Resistor
Local LEDs
Alarm Relay
Fault Relay
Current Output
Maximum Range (IR)
(to alarm <10 s for a 0.1 m
Maximum Range (UV and UVIR)
(to alarm <10 s for a 0.09 m
Alarm Response Time
MAN0987_Iss 2_09/16
CERTIFICATION
SPECIFICATIONS
FSL100 General Specifications
DC 12–24 V (10–28 VDC)
25 mA at 24 VDC
+/- 75 mA at 24 VDC
<10 sec
Selectable LEDs and relays latching/non latching, factory
setting: latching
- a fire control panel by means of end of line (EOL) and alarm
resistor (current increase)
- a device that can take relay outputs
- a PLC with a 0–20 mA input
To match the fire control panel, free terminals dedicated for
the resistors are available
Note: the alarm and EOL resistors must be rated 2 W minimum
each and the total power dissipation of both alarm and EOL resistors
should not exceed 2 W
continuous green: normal operation
continuous yellow: fault (blinking yellow: repeated self-test after a
self-test fault)
continuous red: alarm
De-energized during normal operation, no alarm, SPDT, 30 VDC –
2 A, 60 W max.
Energized during normal operation, no fault, SPDT, 30 VDC – 2 A,
60 W max.
Standard available 0-20 mA (stepped, sinking, non-
isolated) 0 mA power fault / microprocessor fault
2 mA optical fault
4 mA normal operation
20 mA Alarm
35 m/115 ft. (FSL100-IR3)
2
n-heptane fire)
23 m/75 ft. (FSL100-UV and FSL100-UVIR)
2
n-heptane fire)
8 to 30 s.
38