Vote Count - Honeywell FSL100-IR3 Technical Handbook

Fsl100 series
Table of Contents

Advertisement

4.7 Vote Count

FSL100 flame detectors will not give an alarm until several different alarm criteria occur at the same time, and the probability of
a false alarm is very low. The flame detector is therefore suitable for relay activated actions (i.e. drenching) based on the signal
of one flame detector.
However, 'voting' may be demanded in a functional specification, in which case the 'voting-system' may be applied; i.e., the
flame detectors may be mounted in multiples, as shown in the example below where an alarm output would be dependent on
the controller receiving confirmatory alarm inputs from at least two of the available detectors.
A good example of voting would be in a Server room or process room that uses inert gas drenching to replace oxygen in the
atmosphere, and the voting of any 2 out of the 4 flame detectors should be mandated before the relay output can be triggered.
Note: The fire control panel or PLC must be able to support the two detector voting system.
A flame detector is a line of sight detector so voting with just two flame detectors in not reliable. The redundant
flame detector in the opposite corner cannot be used for a 2 detector dependent output because a flame
occurring in a shadow area would not be seen by the second detector until the fire is well established. In this
case the second flame detector will give an alarm too late or not at all.
MAN0987_Iss 2_09/16
INSTALLATION
Monitored object
Figure 8.
Voting Arrangement Using Four Detectors
Caution
12
FSL100 Series Flame Detectors
Technical Handbook

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fsl100-uvFsl100-tlxFsl100-uvirFsl100-sm21Fsl100-tl

Table of Contents