ABB ACS150 series User Manual page 127

0.37...4kw; 0.5...5 hp
Hide thumbs Also See for ACS150 series:
Table of Contents

Advertisement

126
Parameters in the Long parameter mode
Index Name/Selection
9905
MOTOR NOM VOLT
200 V E units/
230 U units:
100...300 V
400 V E units /
460 V U units:
230...690 V
9906
MOTOR NOM CURR
0.2...2.0 · I
2N
9907
MOTOR NOM FREQ
10.0...500.0 Hz
9908
MOTOR NOM SPEED Defines the nominal motor speed. Must be equal to the value on the motor
50...30000 rpm
9909
MOTOR NOM
POWER
0.2...3.0 · P
kW/hp
N
Actual signals and parameters
Description
Defines the nominal motor voltage. Must be equal to the value on the motor
rating plate. The drive cannot supply the motor with a voltage greater than
the input power voltage.
Note that the output voltage is not limited by the nominal motor voltage but
increased linearly up to the value of the input voltage.
Output voltage
Input voltage
9905
WARNING! Never connect a motor to a drive which is connected to power
line with voltage level higher than the rated motor voltage.
Voltage.
Note: The stress on the motor insulations is always dependent on the drive
supply voltage. This also applies to the case where the motor voltage rating
is lower than the rating of the drive and the supply of the drive.
Defines the nominal motor current. Must be equal to the value on the motor
rating plate.
Current
Defines the nominal motor frequency, that is the frequency at which the
output voltage equals the motor nominal voltage:
Field weakening point = Nom. frequency · Supply voltage / Mot nom. voltage
Frequency
rating plate.
Speed
Defines the nominal motor power. Must equal the value on the motor rating
plate.
Power
Output frequency
9907
Def
200 V
E units:
200 V
230 V
U units:
230 V
400 V
E units:
400 V
460 V
U units:
460 V
I
2N
E: 50.0 Hz /
U: 60.0 Hz
Type
dependent
P
N