Parameters in the Long parameter mode
Index Name/Selection
11 = DI3U,4D(RNC)
12 = DI3U,4D(NC)
14 = AI1+POT
15 = AI1*POT
16 = AI1-POT
17 = AI1/POT
19 = INTERNAL
31 = DI4U,5D(NC)
32 = FREQ INPUT
4011
INTERNAL SETPNT
x...x
4012
SETPOINT MIN
-500.0...500.0%
4013
SETPOINT MAX
-500.0...500.0%
4014
FBK SEL
1 = ACT1
2 = ACT1-ACT2
Description
Digital input DI3: Reference increase. Digital input DI4: Reference decrease.
Stop command resets the reference to zero. When this selection becomes
active (in change from EXT1 to EXT2), the reference initializes to the value
used when this control location (and this selection) was active the last time.
Digital input DI3: Reference increase. Digital input DI4: Reference decrease.
The program stores the active reference (not reset by a stop command).
When this selection becomes active (in change from EXT1 to EXT2), the
reference initializes to the value used when this control location (and this
selection) was active the last time.
Reference is calculated with the following equation:
REF = AI1(%) + POT(%) - 50%
Reference is calculated with the following equation:
REF = AI(%) · (POT(%) / 50%)
Reference is calculated with the following equation:
REF = AI1(%) + 50% - POT(%)
Reference is calculated with the following equation:
REF = AI1(%) · (50% / POT (%))
A constant value defined by parameter
See selection DI3U,4D(NC).
Frequency input
Selects a constant value as process PID controller reference, when
parameter
4010
SET POINT SEL value is set to 19 (INTERNAL).
Unit and range depend on the unit and scale defined by parameters
UNITS and
4007
UNIT SCALE.
Defines the minimum value for the selected PID reference signal source. See
parameter
4010
SET POINT SEL.
Value in percent.
Example: Analog input AI1 is selected as the PID reference source (value of
parameter
4010
SET POINT SEL is 1 = AI1). The reference minimum and
maximum correspond to the
settings as follows:
Ref
MAX > MIN
4013
(MAX)
4012
(MIN)
1302
1301
Defines the maximum value for the selected PID reference signal source.
See parameters
4010
SET POINT SEL and
Value in percent
Selects the process actual value (feedback signal) for the process PID
controller: The sources for the variables ACT1 and ACT2 are further defined
by parameters
4016
ACT1 INPUT and
ACT1
Subtraction of ACT1 and ACT 2
4011
INTERNAL SETPNT
1301
MINIMUM AI1 and
1302
Ref
4012
(MIN)
4013
(MAX)
AI1 (%)
1301
4012
SETPOINT MIN.
4017
ACT2 INPUT.
Def
40
4006
0.0%
MAXIMUM AI1
MIN > MAX
AI1 (%)
1302
100.0%
1 = ACT1
Actual signals and parameters
121