4 Installation
4.2

Mounting the indoor unit

4.2.1

To install the indoor unit

1 Bring the unit on the pallet as close as possible to its installation
place.
2 Lift the indoor unit from the pallet and place it on the floor.
2
1
3 Slide the indoor unit into position. Make sure that the side
support bolts are present when handling the unit.
4 Unlink the heat pump module from the outer frame. ONLY
remove the side support bolts!
Installation manual
6
210kg
NOTICE
Do NOT throw away any bolts. They need to be re-inserted
when transport or heavy manipulation is required.
5 Open the front plate of the unit. If needed, the nylon bands for
lifting can be used.
6 Adjust the height of the 4 leveling feet of the outer frame to
compensate for floor irregularities. The maximum allowed
deviation is 1°.
NOTICE
To avoid structural damage on unit, ONLY move the unit
when levelling feet are at their lowest position.
NOTICE
For optimum sound reduction, carefully check if there is no
gap between the bottom frame and the floor.
7 Adjust the height of the 2 front leveling feet of the inner frame to
compensate for irregularities.
CAUTION
Check that the heat pump module does NOT touch the
outer casing.
Daikin Altherma ground source heat pump
≤1°
EGSQH10S18AA9W
4P351747-1F – 2016.06