Meaning of the LED displays
The following tables explain the meaning of the status and error displays. Remedial
measures for diagnostic alarms can be found in section Diagnostic alarms (Page 20).
RUN and ERROR LED
Table 5- 1
Status and error displays RUN and ERROR
LED
RUN
ERROR
Off
Off
Flashes
Off
On
Off
On
Flashes
Flashes
Flashes
PWR LED
Table 5- 2
PWR status display
LED PWR
Off
On
CHx LED
Table 5- 3
CHx status display
LED CHx
Off
On
DQ 8x230VAC/5A ST Digital Output Module (6ES7522-5HF00-0AB0)
Manual, 07/2014, A5E03485590-AC
Meaning
Voltage missing or too low at backplane bus
The module starts and flashes until the valid
parameter assignment is set.
Module is configured
Indicates module error because supply voltage
L+ is missing
Hardware defective
Meaning
Supply voltage L+ too low or missing
Supply voltage L+ is present and OK
Meaning
0 = Status of the output signal
1 = Status of the output signal
Interrupts/diagnostics alarms
5.1 Status and error displays
Remedy
Switch on the CPU and/or the system pow-
er supply modules.
Verify that the U connectors are inserted.
Check to see if too many modules are in-
serted.
---
Evaluate the diagnostics data and eliminate the
error.
Replace the module.
Remedy
Check the L+ supply voltage.
---
Remedy
---
---