Set a limitation towards the power consumption from the system (e.g. budget control, limit power consumption during peak moments, ...).
3 different demand setting can be selected by using terminal X801M:
•
Demand 1 → Close contact between COM and contact 1
•
Demand 2 → Close contact between COM and contact 2
•
Demand 3 → Close contact between COM and contact 3
Demand 1
Power consumption limitation in function of setting on DS1.
DS1 Setting
1
2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Demand 2
Power consumption limitation set to 40%.
Demand 3
Forced thermostat OFF.
5.2.3.3. Setting for Low Humidity Application
Can be set when using the RZAG-L units for year round cooling in low humidity applications such as computer rooms (EDP rooms), technical rooms, etc...to increase the capacity of the unit.