Custom Code Setting; Function Setting - Fujitsu AUXB07L Installation Manual

Vrf system indoor unit compact cassette type
Hide thumbs Also See for AUXB07L:
Table of Contents

Advertisement

Example If 4 indoor units are connected.
Indoor unit
Indoor unit
RC AD SW
RC AD SW
0
1
Remote
controller
RC AD SW
0
1
Address
0
1
RC AD SW
8
9
Address
8
9

7.2. Custom code setting

Selecting the custom code prevents the indoor unit mix-up.
(Up to 4 codes can be set.)
Perform the setting for both the indoor unit and the remote
controller.
Confusion
Indoor
unit
Remote
controller
• Custom code setting for indoor unit
Set the DIP SW SET 3 SW1 , SW2, referring to the Table B.
SW
SW
SW
1
2
Table B
A (Factory setting)
DIP SW
OFF
SET 3 SW1
DIP SW
OFF
SET 3 SW2
• Do not operate any switches other than prescribed, as it can
cause the unit to operate improperly or malfunction.
En-14
Indoor unit
Indoor unit
RC AD SW
RC AD SW
2
2
3
4
5
2
3
4
5
A
B
C
D
10
11
12
13
Code change
A
B
A
B
Dip switch "SET3"
SW
3
4
Custom code
B
C
ON
OFF
OFF
ON
CAUTION

7.3. Function setting

• FUNCTION SETTING can be performed with the wired or
wireless remote control.
3
(The remote control is optional equipment)
• Refer to the wired or wireless remote control manual for
detailed setting information. (Set IU AD ,REF AD SW to 0)
• Refer to "7.1. Setting the address." for indoor unit address
and refrigerant circuit address settings.
• Turn the power of the indoor unit ON before starting the
setting.
6
7
6
7
* Turning on the power indoor units initializes EEV, so make
E
F
sure the piping air tight test and vacuuming have been
14
15
conducted before turning on the power.
* Also check again to make sure no wiring mistakes were
made before turning on the power.
Function details
Function
Function
number
Filter
indicator
interval
C
D
C
D
Filter
indicator
action
Ceiling
airflow
Vertical
airflow
direction
Cool air
tem-
perature
trigger
Hot air
tem-
perature
trigger
Auto
D
restart
ON
ON
External
control
Setting
Default
number
Adjust the filter cleaning interval
00
Default
notification. If the notification is
11
too early, change to setting 01. If
01
Longer
the notification is too late, change
02
Shorter
to setting 02.
00
Enable
01
Disable
Enable or disable the filter
Display
13
indicator. Setting 02 is for use
only on
with a central remote control.
02
central
remote
control
Regulate the airflow according
00
Default
to the needs of the installation
20
location. When set to 01, the air
High
01
flow will be stronger.
Ceiling
Adjust the vertical airflow
00
Default
direction. All airflow direction
23
louvers are adjusted together.
01
Raise
(Cassette type only)
Adjust the cool air trigger
00
Default
temperature. To lower the trigger
30
temperature, use setting 01. To
01
Adjust (1)
raise the trigger temperature, use
02
Adjust (2)
setting 02.
Adjust the hot air trigger
00
Default
temperature. To lower the trigger
01
Adjust (1)
temperature by 6 degrees C, use
31
setting 01. To lower the trigger
02
Adjust (2)
temperature by 4 degrees C, use
setting 02. To raise the trigger
03
Adjust (3)
temperature, use setting 03.
00
Enable
Enable or disable automatic
40
system restart after a power
01
Disable
outage.
Allow an external controller to
start or stop the system, or to
00
Start/Stop
perform an emergency shutdown.
46
* If an emergency shutdown is
Emergency
01
stop
Details
performed from an external
controller, all refrigerant systems
will be disabled.