Fujitsu ARA12LATN Service Instruction page 110

Duct type inverter indoor / outdoor units
Table of Contents

Advertisement

8-5. FUNCTION SETTING
8-5-1 INDOOR UNIT
Follow the instructions in the Local Setup Procedure, which is supplied with the remote control,
in accordance with the installed condition.
After the power is turned on, perform the Function Setting on the remote control.
The settings may be selected between the following two: Function Number or Setting Value.
Settings will not be changed if invalid numbers or setting values are selected.
1-1. Setting the Static Pressure
Setting Description
Normal
High static pressure 1
High static pressure 2
High static pressure 3
Determine the wind volume in each mode i.e., applicable range of static pressure,
refering to TECHNICAL MANUAL.
1-2. Setting the Cooler Room Temperature Correction
Depending on the installed environment, the room temperature sensor may require a correction.
The settings may be selected as shown in the table below.
Setting Description
Standard
Lower control
1-3. Setting the Heater Room Temperature Correction
Depending on the installed environment, the room temperature sensor may require a correction.
The settings may be changed as shown in the table below.
Setting Description
Standard
Lower control
Slightly warmer control
Warmer control
(
Function Number
Setting Value
21
(
Function Number
Setting Value
30
(
Function Number
Setting Value
31
08-12
Factory setting)
00
01
02
03
Factory setting)
00
01
Factory setting)
00
01
02
03