Blower Prover Switch - Settings - A.O. Smith SERIES 120 Service Handbook

Commercial gas water heaters
Hide thumbs Also See for SERIES 120:
Table of Contents

Advertisement

OPERATION AND SERVICE

BLOWER PROVER SWITCH - SETTINGS

Vent Connection
Blower Prover Switch
Exhaust/Outlet
Optional Hot Water Outlet
Blower (Draft Inducer)
Figure 15
Table 4
BLOWER PROVER SWITCH TABLE
BTR Model
Pressure Setting to Close Switch (Inches W.C.)
500/A
-2.85" ± 0.13"
NOTE: The Blower Prover Switch contacts are normally open and will close on a fall in
pressure. This will be a negative pressure (i.e., a vacuum).
Servicing should only be performed by a Qualifi ed Service Agent